3 Installation
3.1 Mechanical Installation
Select the best possible operation site by considering the
following:
Ambient operating temperature
Installation method
How to cool the unit
Position of the frequency converter
Cable routing
Power source supplying correct voltage and
necessary current
Motor current rating within the maximum current
from the frequency converter
Correct rating of external fuses and circuit
breakers
Cooling and Mounting:
Top and bottom clearance for air cooling must be
provided, see Table 3.1 for clearance requirements
Derating for temperatures starting from 45°C and
elevation 1000m above sea level must be
considered. See the equipment Design Guide for
detailed information.
Enclosure
J1-J5 J6/J7
Clearance above and below the
unit [mm]
100-200
Table 3.1 Minimum Airflow Clearance Requirements
Mount the unit vertically
IP20 units (but NOT IP21 units) allow side by side
installation
Improper mounting can result in over heating
and reduced performance
Use the slotted mounting holes on the unit for
wall mounting, when provided
See 8.4 Connection Tightening Torques for proper
tightening specifications.
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
10 MG06A102 - VLT
®
is a registered Danfoss trademark
33

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLTAutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLTAutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLTAutomationDrive FC 360
CategoryController
LanguageEnglish

Related product manuals