1 Quick Start
WARNING
Improper use could result in death, serious injury,
equipment, or property damage. Before installing or using
the equipment, read 1 Safety and 3 Installation carefully!
1.1 Identification and Variants
Confirm that the equipment matches the requirements
and ordering information by checking power size, voltage
and overload data on the name plate of the frequency
converter.
130BC435.11
CHASSIS/IP20
VLT
MADE BY DANFOSS
IN CHINA
AutomationDrive
www.danfoss.com
R
T/C: FC-360HK37T4E20H2BXCDXXSXXXXAXBX
P/N: 134F2970 S/N: 691950A240
0.37 kW 0.5HP High Overload
IN: 3x380-480V 50/60Hz 1.24/0.99A
OUT: 3x0-Vin 0-500Hz 1.2/1.1A(Tamb. 45 C)
o
1
2
3
CAUTION:
SEE MANUAL
WARNING:
AND LAODSHARING BEFORE SERVICE
STORED CHARGE DO NOT TOUCH UNTIL 4 MIN. AFTER
DISCONNECTION
RISK OF ELECTRIC SHOCK-DUAL SUPPLY DISCONNECT MAINS
Illustration 1.1 Name Plate 1 and 2
1) Typecode
2) Ordering Number
3) Specifications
1-6: Product Name
7: Overload H: Heavy Duty
Q: Normal Duty
1)
8-10: Power Size 0.37-75 kW e.g.
K37: 0.37 kW
2)
1K1: 1.1 kW
11K: 11 kW etc.
11-12: Voltage Class 4: 380-480 V
13-15: IP Class E20: IP20
16-17: RFI H2: C3 Class
18: Braking Chopper X: No
B: Built-in
4)
19: LCP X: No
20: PCB Coating 3: 3C3
21: Mains Terminals D: Load Sharing
29-30: Embedded Fieldbus AX: No
A0: Profibus
3)
AL: Profinet
3)
Table 1.1 Type Code: Selection of Different Features and Options
See for options and accessories.
1) Only 11-75 kW for Normal Duty variants. Fieldbus unavailable for
Normal Duty.
2) For all power sizes see 2.4 Frame Sizes and Power Ratings
3) Not available yet.
4) 0.37-22 kW with built-in braking chopper. 30-75 kW external
braking chopper only.
130BC437.10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
F C - 3 6 0 H T 4 E 2 0 H 2 X X C D X X S X X X X A X B X
Q B 0
L
A
A
Illustration 1.2 Typecode string
Quick Start
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A102 - VLT
®
is a registered Danfoss trademark 3
1 1