8 Specifications
8.1 Power-dependent Specifications
8.1.1 Mains Supply 3 x 380-480 V AC
Frequency converter
Typical Shaft Output [kW]
HK 37
0.37
HK 55
0.55
HK75
0.75
H1K1
1.1
H1K5
1.5
H2K2
2.2
H3K0
3
H4K0
4
H5K5
5.5
H7K5
7.5
Enclosure IP20 J1 J1 J1 J1 J1 J1 J2 J2 J2 J3
Output current
Shaft output [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5
Continuous
(3 x 380-439 V) [A]
1.2 1.7 2.2 3 3.7 5.3 7.2 9 12 15.5
Continuous
(3 x 440-480 V) [A]
1.1 1.6 2.1 3 3.4 4.8 6.3 8.2 11 14
Intermittent
(60 s overload) [A]
1.9 2.7 3.5 4.8 5.9 8.5 11.5 14.4 19.2 24.8
Continuous kVA
(400 V AC) [kVA]
0.84 1.18 1.53 2.08 2.57 3.68 4.99 6.24 8.32 10.74
Continuous kVA
(460 V AC) [kVA]
0.91 1.34 1.75 2.5 2.8 4.01 5.24 6.82 9.15 11.64
Max. input current
Continuous
(3 x 380-439 V) [A]
1.2 1.6 2.1 2.6 3.5 4.7 6.3 8.3 11.2 15.1
Continuous
(3 x 440-480 V) [A]
1.0 1.2 1.8 2.0 2.9 3.9 4.3 6.8 9.4 12.6
Intermittent
(60 s overload) [A]
1.9 2.6 3.4 4.2 5.6 7.5 10.1 13.3 17.9 24.2
Additional specifications
Max. cable cross section (mains,
motor, brake and load sharing)
[mm
2
(AWG)]
2)
4 mm
2
Estimated power loss
at rated max. load [W]
3)
52.36 113.85 150.75
Weight,
enclosure IP20
2.3 2.3 2.3 2.3 2.3 2.5 3.6 3.6 3.6 4.1
Efficiency
4)
97.62% 98% 98%
Table 8.1 Mains Supply 3 x 380-480 V AC - Heavy Duty
1)
Frequency converter
Typical Shaft Output [kW]
H11K
11
H15K
15
H18K
18.5
H22K
22
H30K
30
H37K
37
H45K
45
H55K
55
H75K
75
IP20 J4 J4 J5 J5 J6 J6 J6 J7 J7
Output current
Continuous (3 x 380-439 V) [A] 23 31 37 42.5
Continuous (3 x 440-480 V) [A]
21 27 34 40
Intermittent (60 s overload) [A] 34.5 46.5 55.5 63.8
Continuous kVA (400 V AC) [kVA] 15.94 21.48 25.64 29.45
Continuous kVA 460 V AC) [kVA] 17.46 22.45 28.27 33.26
Max. input current
Continuous (3 x 380-439 V ) [A] 22.1 29.9 35.2 41.5
Continuous (3 x 440-480 V) [A] 18.4 24.7 29.3 34.6
Intermittent (60 s overload) [A] 33.2 44.9 52.8 62.3
Additional specifications
Max. cable size (mains, motor,
brake) [mm
2
/ AWG]
2)
16 mm
2
16 mm
2
16 mm
2
16 mm
2
50 mm
2
50 mm
2
50 mm
2
50 mm
2
85 mm
2
Estimated power loss at rated max.
load [W]
3)
Weight enclosure IP20 [kg] 9.4 9.5 12.3 12.5
Efficiency
4)
Table 8.2 Mains Supply 3x380-480 V AC - Heavy Duty
1)
Specifications
VLT
®
AutomationDrive FC 360 Quick Guide
36 MG06A102 - VLT
®
is a registered Danfoss trademark
88

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLTAutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLTAutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLTAutomationDrive FC 360
CategoryController
LanguageEnglish

Related product manuals