8.3.3 CE Compliance
Fuses or Circuit Breakers are mandatory to comply with IEC
60364. Danfoss recommend using a selection of the
following.
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical), 480 V depending
on the frequency converter voltage rating. With the proper
fusing the frequency converter short circuit current rating
(SCCR) is 100,000 Arms.
Frame Size Power [kW] gG
J1
0.37-1.1
101.5
2.2
J2
3.0
254.0
5.5
J3 7.5 32
J4 11-15 50
J5
18.5
80
22
J6
30
16037
45
J7
55
250
75
Table 8.4 CE Fuse, 380-480 V, Frame Sizes J1-J7
The circuit breakers below are suitable for use on a circuit
capable of delivering 35,000 Arms (symmetrical), 480 V
depending on the frequency converter voltage rating. With
the proper fusing the frequency converter short circuit
current rating (SCCR) is 35,000 Arms.
Frame Size
Power [kW] EATON
J1
0.37-1.1
Moller
PKZM0-16
1.5
2.2
J2
3.0
NZMN-1-A-254.0
5.5
J3 7.5 NZMN-1-A-32
J4 11-15 NZMN-1-A-50
J5
18.5
NZMN-1-A-80
22
J6
30
NZMN-1-A-16037
45
J7
55
NZMN-1-A-250
75
Table 8.5 CE Circuit Breakers, 380-480 V, Frame Sizes J1-J7
UL Compliance
Fuses or Circuit Breakers are mandatory to comply with
NEC 2009. We recommend using a selection of the
following
The circuit breakers below are suitable for use on a circuit
capable of delivering 100,000 Arms (symmetrical), 480 V
depending on the frequency converter voltage rating. With
the proper fusing the drive Short Circuit Current Rating
(SCCR) is 100,000 Arms.
The circuit breakers below are suitable for use on a circuit
capable of delivering 35,000 Arms (symmetrical), 480 V
depending on the frequency converter voltage rating. With
the proper fusing the frequency converter short circuit
current rating (SCCR) is 35,000 Arms.
Frame Size Power [kW] Bussmann
J1
0.37-1.1
FRS-R-161.5
2.2
J2
3.0
FRS-R-254.0
5.5
J3 7.5 FRS-R-30
J4 11-15 FRS-R-50
J5
18.5
FRS-R-80
22
J6
30
FRS-R-15037
45
J7
55
FRS-R-250
75
Table 8.6 UL Fuse, 380-480 V, Frame Sizes J1-J7
Frame Size
Power [kW] EATON
J1
0.37-1.1
XTPR016BC1+XTPAXLSA1.5
2.2
J2
3.0
NZMN-2-A-25-NA4.0
5.5
J3 7.5 NZMN-2-A-32-NA
J4 11-15 NZMN-2-A-50-NA
J5
18.5
NZMN-2-A-80-NA
22
J6
30
NZMN-2-A-160-NA37
45
J7
55
NZMN-2-A-250-NA
75
Table 8.7 UL Circuit Breakers, 380-480 V, Frame Sizes J1-J7
Specifications
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A102 - VLT
®
is a registered Danfoss trademark 43
8 8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLTAutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLTAutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLTAutomationDrive FC 360
CategoryController
LanguageEnglish

Related product manuals