Function Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
Feedback Speed
Error
100 RPM
4-32 Motor
Feedback Loss
Timeout
5 s
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start Event
[19] Warning
13-02 Stop Event
[44] Reset
key
13-10 Comparato
r Operand
[21] Warning
no.
13-11 Comparato
r Operator
[1] ≈*
13-12 Comparato
r Value
90
13-51 SL
Controller Event
[22]
Comparator 0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80] SL digital
output A
* = Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The SLC
monitors Warning 90 and in
the case that Warning 90
becomes TRUE then Relay 1 is
triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 sec. then the drive
continues and the warning
disappears. But Relay 1 will still
be triggered until [Reset] on
the LCP.
Table 5.7 Using SLC to Set a Relay
Wiring Examples
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A102 - VLT
®
is a registered Danfoss trademark 29