EasyManuals Logo
Home>Delta Electronics>DC Drives>AC Servo Drive ASDA-AB

Delta Electronics AC Servo Drive ASDA-AB User Manual

Delta Electronics AC Servo Drive ASDA-AB
357 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #195 background imageLoading...
Page #195 background image
Chapter 7 Servo Parameters|ASDA-AB Series
7-46
Revision January 2009
P1 - 47
HMOV Homing Mode Communication Addr.: 012FH
Default: 00 Related Section:
Applicable Control Mode: ALL Section 12.8
Unit: N/A
Range: 00 ~ 1225
Settings:
not used
A
B
C
D
A=0: Forward homing (CCWL as “Home”)
A=1: Reverse homing (CWL as “Home”)
A=2: Forward homing (ORGP as “Home”)
A=3: Reverse homing (ORGP as “Home”)
A=4: Forward to find Z-phase pulse and regard Z-
phase pulse as “Home”
A=5: Reverse to find Z-phase pulse and regard Z-
phase pulse as “Home”
B=0: Return to find Z-phase pulse during homing
B=1: Do not return and go forward to find Z-phase pulse during homing
B=2: Positioning at home sensor position or Z-phase pulse during homing (it only can be
used when A=2, 3, 4 or 5)
C=0: Disable homing function.
C=1: Enable homing function automatically after power supplies to the servo drive.
C=2: Enable homing function by SHOM.
D=0: After detecting “Home”, the motor will decelerate and return to “Home”.
D=1: After detecting “Home”, the motor will decelerate and stop in the forward direction.
Other: Reserved
Example:
Power supplies to the servo drive, after servo on, immediately perform the homing function and
use CCWL as “Home”.
1: Refer to P1-01 for forward and reverse direction
2: CWL and CCWL (refer to Table 7.A) should be assigned into internal input contact (refer to
P2-10 ~ P2-17) and connected to external limit switch corresponding to internal contact.
3: Set the value of P1-47 to 100.
4: Restart power on again, after servo on, the drive will immediately perform homing function
automatically according to the assigned direction.
NOTE
1) When using CWL and CCWL as “Home”, these two inputs will return to limit stop protect
function after homing function is completed. It is recommended to set CWL and CCWL at the
terminal of equipment to avoid these two inputs may be triggered during normal operation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics AC Servo Drive ASDA-AB and is the answer not in the manual?

Delta Electronics AC Servo Drive ASDA-AB Specifications

General IconGeneral
BrandDelta Electronics
ModelAC Servo Drive ASDA-AB
CategoryDC Drives
LanguageEnglish

Related product manuals