5
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-75
11 - 07
Wakeup Frequency
Factory Setting: 0.00
Settings 0.00 to Fmax Unit: 0.01Hz
When actual output frequency H < Pr.11-06 and time exceeds the setting of Pr.11-05,
AC drive will be in sleep mode.
When actual frequency command > Pr.11-07 and time exceeds the setting of Pr.11-05,
Ac drive will restart.