Chapter 5 Parameters_VFD-B Series
Revision 10/2005, BE13, SW V4.08 5-49
03 - 10
Desired Frequency Attained 2 Unit: 0.01
Settings 0.00 to 400.00 Hz Factory Setting: 0.00
If a multi-function output terminal is set to function as Desired Frequency Attained 1 or 2 (Pr.03-00 to Pr.03-
03 = 09 or 22), then the output will be activated when the programmed frequency is attained.
-2Hz
4Hz
2Hz
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
detection
range
Frequency
master
frequency
desired
frequency
detection range
detection
range
DC braking time
during stop
Time
waiting time
for
frequency
run/stop
master freq. attained
(output signal)
desired freq. attained
setting 03 zero speed indication
setting 24 zero speed indication
output timing chart of multiple function terminals
when setting to frequency attained or zero speed indication
03 - 05
Analog Output Signal (AFM)
Factory Setting: 00
Settings 00 Analog Frequency Meter (0 to Maximum Output Frequency)
01 Analog Current Meter (0 to 250% of rated AC motor drive current)
02 Output voltage (0 to Pr.01-02)
03 Output frequency command (0 to Maximum Frequency)
04 Output motor speed (0 to the Maximum Frequency)
05 Load power factor (cos90
o
to 0
o
)
This parameter sets the function of the AFM output 0~+10VDC (ACM is common).