Chapter 5 Parameters_VFD-B Series
5-38
Revision 10/2005, BE13, SW V4.08
02 – 01
aSource of First Operation Command
Factory Setting: 00
Settings 00 Digital keypad (PU01)
01 External terminals. Keypad STOP/RESET enabled.
02 External terminals. Keypad STOP/RESET disabled.
03 RS-485 serial communication (RJ-11). Keypad STOP/RESET enabled.
04 RS-485 serial communication (RJ-11). Keypad STOP/RESET disabled.
02 - 14
aSource of Second Operation Command
Factory Setting: 00
Settings 00 Digital keypad (PU01)
01 External terminals. Keypad STOP/RESET enabled.
02 External terminals. Keypad STOP/RESET disabled.
03 RS-485 serial communication (RJ-11). Keypad STOP/RESET enabled.
04 RS-485 serial communication (RJ-11). Keypad STOP/RESET disabled.
When the AC motor drive is controlled by external terminal, please refer to Pr.02-05 for details.
The first /second frequency/operation command is enabled/disabled by Multi Function Input Terminals.
Please refer to of Pr.04-04 ~ 04-09.
02 - 10
aSource of the Master Frequency Command
Factory Setting: 00
Settings 00 Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs UP/DOWN.
Last used frequency saved.
01 AVI 0 ~ +10VDC
02 ACI 4 ~ 20mA
03 AUI -10 ~ +10VDC
04 RS-485 serial communication (RJ-11). Last used frequency saved.

Table of Contents

Other manuals for Delta VFD110B43A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD110B43A and is the answer not in the manual?

Delta VFD110B43A Specifications

General IconGeneral
BrandDelta
ModelVFD110B43A
CategoryDC Drives
LanguageEnglish

Related product manuals