Chapter 5 Parameters_VFD-B Series
Revision 10/2005, BE13, SW V4.08 5-77

In Pr.06-08 to Pr.06-11 the four most recent faults that occurred, are stored. After removing the cause of
the fault, use the reset command to reset the drive.
06 - 12
Under-Current Detection Level Unit: 1
Settings 00 ~ 100% Factory Setting: 00
00 Disabled
06 - 13
Under-Current Detection Time Unit: 0.1
Settings 0.1~ 3600.0 sec Factory Setting: 10.0
06 - 14
Under-Current Detection Mode
Factory Setting: 00
Settings 00 Warn and keep operating
01 Warn and ramp to stop
02 Warn and coast to stop
03 Warn, after coast to stop, restart (delay 06-15 setting time)
06 - 15
Under-Current Detection Restart Delay Time Unit: 1
Settings 1~600 min Factory Setting: 10

If output current is lower than the setting Pr.06-12 for a time that exceeds Pr.06-13 setting during operation,
the AC drive will warn per Pr.06-14 setting. If Pr.06-14 is set to 03, the AC drive will restart after the delay
time set by Pr.06-15 is up.
06 - 16
User-Defined Low-Voltage Detection Level (Lv) Unit: 1
Settings 00 Disabled
230V series: 220 ~ 300VDC Factory Setting: 00
460V series: 440 ~ 600VDC Factory Setting: 00
575V series: 520 ~ 780VDC Factory Setting: 00
06 - 17
User-Defined Low-Voltage Detection Time Unit: 0.1
Settings 0.1~ 3600.0 sec Factory Setting: 0.5

Table of Contents

Other manuals for Delta VFD110B43A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD110B43A and is the answer not in the manual?

Delta VFD110B43A Specifications

General IconGeneral
BrandDelta
ModelVFD110B43A
CategoryDC Drives
LanguageEnglish

Related product manuals