Chapter 2 Installation and Wiring_VFD-B Series
2-26
Revision 10/2005, BE13, SW V4.08
NOTE

If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as possible to
AC drive. EMI can also be reduced by lowering the Carrier Frequency.

When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of
200mA, and not less than 0.1-second detection time to avoid nuisance tripping.
DANGER!
Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it comes in contact
with high voltage.