91
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
Typical Example of Message Format
To read all contact status data on a 32 way SmartAlarm the following message format has to be
repeated 4 times, once for each alarm card node address.
RTU
ADDRESS FUNCTION REGISTER
ADDRESS
No Of
REGISTERS
ERROR CHECK
01 01 00 01 00 08 6C 0C
Example shows message for rst card, Comms address offset 0.
33.3 Read Status – Function 03 – Read Request – Master
Register Address
This is used to address the “start” channel to be read, typically the rst channel “channel 1” contact
status on alarm card would be register address 40001
To read the contact status registers use address range 40001- 40008
To read the alarm status registers use address range 40011- 40018
To read the disable status registers use address range 40021- 40028
Number of Registers
This represents the number of registers (Channels) the master wishes to read. The range is 1- 8.
33.4 Read Status – Function 03 – Read Response - Slave
Byte Count
This represents the number of bytes sent
Data
Data returned depends on register address originally specied by the master.
Register address 40001 - 40008 returns Contact status data
0 = Normal
1 = Abnormal

Table of Contents

Other manuals for Eaton 9372-FB-P Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9372-FB-P Series and is the answer not in the manual?

Eaton 9372-FB-P Series Specifications

General IconGeneral
BrandEaton
Model9372-FB-P Series
CategoryLighting Equipment
LanguageEnglish

Related product manuals