1type vsa12, vsa12b, vsa16, vsa20, and vsa20a operation and installation instructions MN280063EN May 2017
Product information
Introduction
Service Information MN280063EN provides installation
instructions, operating information, and testing procedures
for Eatons Cooper Power™ series three-phase motor-
operated reclosers.
The information contained in this manual is organized into
the following major categories: Safety Information, Product
Information, Specifications and Ratings, Dimensions and
Weights, Installation, Accessories, Operation, and Service
Information.
Read this manual first
Read and understand the contents of this manual and follow
all locally approved procedures and safety practices before
installing or operating this equipment.
Additional information
These instructions cannot cover all details or variations
in the equipment, procedures, or process described nor
provide directions for meeting every possible contingency
during installation, operation, or maintenance. For additional
information, contact your Eaton representative.
Acceptance and initial inspection
This product is completely assembled, tested, and
inspected at the factory. It is carefully calibrated, adjusted,
and in good condition when accepted by the carrier for
shipment.
Upon receipt, inspect the carton for signs of damage.
Unpack the control and inspect it thoroughly for damage
incurred during shipment. If damage is discovered, file a
claim with the carrier immediately.
Handling and storage
Be careful during handling and storage of this equipment to
minimize the possibility of damage. In particular, protect the
bushings and control equipment.
If the unit is to be stored for any length of time before
installation, provide a clean, dry storage area. If the recloser
is to be stored in a humid atmosphere, make provisions to
keep the cabinet heaters energized.
ANSI
®
standards
The VSA recloser is designed and tested in accordance with
ANSI
®
standards: C37.60 and C37.85.
Quality standards
ISO 9001 certified quality management system
Description
A complete assembly consists of the recloser control unit,
the vacuum interrupter assemblies, and the operating
mechanism housing.
Recloser tripping employs stored spring energy. When the
trip solenoid is actuated by the 24 Vdc trip signal, the stored
spring energy is released to open the recloser. The 24 Vdc
trip signal is originated at the recloser control. The 240 Vdc
supply is not required to trip the recloser. An external 240
Vac source is required to operate the drive motor. A 120 Vac
input power supply accessory is also available.
Type VSA reclosers are electronically controlled by Eatons
Cooper Power series recloser controls.

Other manuals for Eaton GridAdvisor Series II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton GridAdvisor Series II and is the answer not in the manual?

Eaton GridAdvisor Series II Specifications

General IconGeneral
BrandEaton
ModelGridAdvisor Series II
CategoryCables and connectors
LanguageEnglish

Related product manuals