Section 3: Initial control programming
This section explains each step for properly completing
initial control programming settings on a CL-7 voltage
regulator control and back panel. Check the System Line
Voltage rating on the regulator nameplate. Refer to the
regulator service manual as identified on the regulator
nameplate for additional information on the regulator.
This section covers standard set-up procedures for controls,
including control replacement. Refer to Programming
and reconfiguring for different voltage systems when
installing/replacing the CL-7 control and reconfiguring the
regulator for a different voltage system.
1. Start with all switches on the control front panel turned
OFF.
2. There are two options for powering the control: internal
power or external power. Select one method and follow
the appropriate step.
a. Internal Power
Turn POWER switch to Internal from the Off position.
b. External Power
Apply external source to the EXTERNAL SOURCE
binding posts: hot lead to black, top binding post;
neutral lead to white, bottom binding post; ground
to green ground binding post. Refer to Section1:
Control Front Panel: Connecting power to external
source terminals for detailed instructions on applying
power to the external source terminals.
Turn POWER switch to External from the Off
position.
Basic programming
Set the parameters in Table3 to program the control
for basic operation. Continue with the steps in Table4
to program the control for reverse power and additional
features.
ote:N After turning on the control and the LCD displays the
results of the Self-Test, press ESC for further keypad
use.
Step-by-step programming instructions are included in
Table3 and Table4. The Instructions column lists keys to
press (i.e.; ENTER, Edit, 7, etc.). Also, italicized instructions
denote a choice or an entry; Value denotes a desired value
entered via the numeric keypads; and following each
“Scroll” is an italicized list of alternatives that appear in the
display, within that function code. Scroll through the list until
the desired alternative is selected, and then press Enter.
Perform a Demand Master Reset (FC 38) after completing
the initial control programming to reset to present demand
values.
ote:N Go to FC 941 to change the language setting.
Table3. Programming for basic operations
Function
code Description Instructions
99 Security Function FUNC, 99, ENTER, Password Admin (default), ENTER
1 Forward Set Voltage FUNC, 1, ENTER, EDIT, Value, ENTER
2 Forward Bandwidth FUNC, 2, ENTER, EDIT, Value, ENTER
3 Forward Time Delay FUNC, 3, ENTER, EDIT, Value, ENTER
4 Forward Line Drop Comp. Resistance FUNC, 4, ENTER, EDIT, Value, ENTER
5 Forward Line Drop Comp. Reactance FUNC, 5, ENTER, EDIT, Value, ENTER
40 Control Identification FUNC, 40, ENTER, EDIT, I. D. number, ENTER
41 Regulator Configuration FUNC, 41, ENTER, EDIT, Scroll - Wye; Delta Lagging; Delta Leading, ENTER
42 Control Operating Mode FUNC, 42, ENTER, EDIT, Scroll - Sequential; Time Integrating; Voltage Averaging, ENTER
43 System Line Voltage FUNC, 43, ENTER, EDIT, Value, ENTER
44 Overall PT Ratio FUNC, 44, ENTER, EDIT, Value, ENTER
44 Internal PT Ratio FUNC 44, Down Arrow, EDIT, Value, ENTER
45 C.T. Primary Rating FUNC, 45, ENTER, EDIT, Value, ENTER
46 Demand Time Interval FUNC, 46, ENTER, EDIT, Value, ENTER
49 Tap-Changer Type FUNC, 49, ENTER, EDIT, Scroll - Cooper QD8; Cooper QD5; Cooper QD3; Cooper Spring
Drive; Cooper Direct Drive; Siemens; General Electric; Howard; LTC -Reinhausen, ITB,
Toshiba, User-Defined, ENTER
50 Calendar/Clock FUNC, 50, ENTER, EDIT, Month, Day, Year, Hour, Minute, ENTER
140 Regulator Type FUNC, 140, ENTER, EDIT, Scroll - Type A; Type B; Type C; Type D, ENTER
144 P.I. ADD-AMP™ High Limit FUNC, 144, ENTER, EDIT, Value, ENTER
145 P.I. ADD-AMP Low Limit FUNC, 145, ENTER, EDIT, Value, ENTER
146 Vin PT Configuration FUNC, 146, ENTER, EDIT, Scroll - Vdiff without RCT2; Vin, Vdiff with RCT2, ENTER
69 Auto Operation Blocking Status FUNC, 69, ENTER, EDIT, Scroll - Normal; Blocked, ENTER
148 Nominal Sec Load voltage FUNC, 141, ENTER, EDIT, Scroll - 120, 240, System Line Voltage ENTER
19
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225003EN April 2018
CL-7 Voltage Regulator Control

Table of Contents

Other manuals for Eaton MET

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton MET and is the answer not in the manual?

Eaton MET Specifications

General IconGeneral
BrandEaton
ModelMET
CategoryCables and connectors
LanguageEnglish

Related product manuals