SV9000 Motor Pump Enhanced Protection Application Page 9 (60)
6 Special parameters, Groups 2—10
6.1 Parameter tables
Group 2, Input signal parameters
Cod
e
Parameter Range Step Default Custom Description Page
2.1 V
in
signal range 0—2 1 0 0 = 0—10 V
1 = Custom setting range
2 = -10—+10 V (can be used only
with Joystick control)
19
2.2 V
in
custom setting min. 0—100% 0.01% 0.00% 19
2.3 V
in
custom setting max. 0—100% 0.01% 100.00% 19
2.4 V
in
signal inversion 0—1 1 0 0 = Not inverted
1 = Inverted
19
2.5 V
in
signal filter time 0 —10s 0.01s 0.1s 0 = No filtering 19
2.6 I
in
signal range 0—2 1 0 0 = 0—20 mA
1 = 4—20 mA
2 = Custom setting range
19
2.7 I
in
custom setting min. 0—100% 0.01% 0.00% 20
2.8 I
in
custom setting max. 0—100% 0.01% 100.00% 20
2.9 I
in
signal inversion 0—1 1 0 0 = Not inverted 20
2.10 I
in
signal filter time 0 —10s 0.01s 0.1s 0 = No filtering 20
2.11 V
in
minimum scaling -320.00% —
+320.00%
0% 0.01 0% = no minimum scaling 20
2.12 V
in
maximum scaling -320.00% —
+320,00 %
100% 0.01 100% = no maximum scaling 20
2.13 I
in
minimum scaling -320.00% —
+320.00%
0% 0.01 0% = no minimum scaling 20
2.14 I
in
maximum scaling -320.00% —
+320.00%
100% 0.01 100% = no maximum scaling 20
2.15 Free analog input,
signal selection
0—4 1 0 0 = Not use
1 = V
in
(analog voltage input)
2 = I
in
(analog current input)
3 = A
in1
(option board)
4 = A
in2
(option board)
21
2.16 Free analog input,
function
0—4 1 0 0 = No function
1 = Reduces current limit (par. 1.7)
2 = Reduces DC-braking current
3 = Reduces acc. and decel. times
4 = Reduces torque supervis. limit
21
2.17 Motorized potentiometer
ramp time
0.1—2000.0
Hz/s
0.1
Hz/s
10.0
Hz/s
23
2.18 Option board A
in1
signal
inversion
0—1 1 0 0 = Not inverted
1 = Inverted
23
2.19 Option board A
in1
signal
filter time
0—10s 0.01s 0.1s 0 = No filtering 23
2.20 Option board A
in2
signal
range
0—2 1 0 0 = 0—20 mA
1 = 4—20 mA
2 = 0—10 V
23
2.21 Option board A
in2
signal
inversion
0—1 1 0 0 = Not inverted
1 = Inverted
23
2.22 Option board A
in2
signal
filter time
0 —10s 0.01s 0.1s 0 = No filtering 23