Page 4 (60) Motor Pump Enhanced Protection Application SV9000
5 Basic Parameters, Group 1
5.1 Parameter Table
Code Parameter Range Step Default Custom Description Page
1.1 Minimum frequency 0—120/500 Hz 1 Hz 0 Hz 5
1.2 Maximum
frequency
0—120/500 Hz 1 Hz 50 Hz * 5
1.3 Acceleration time 1 0.1—3000 s 0.1 s 3 s Time from f
min
(1. 1) to f
max
(1. 2) 5
1.4 Deceleration time 1 0.1—3000 0.1 s 3 s Time from f
max
(1. 2) to f
min
(1. 1) 5
0 = V
in
3 = V
in
- I
in
1 = I
in
4 = I
in
- V
in
2 = V
in
+ I
in
5 = V
in
* I
in
6 = V
in
joystick control
7 = I
in
joystick control
8 = Signal from internal motor pot.
9 = Signal from internal motor pot.
reset if SV9000 unit is stopped
10 = Signal from internal motor pot.
(stored in memory over utility
break)
11 = Min (V
in
, I
in
)
12 = Max (V
in
, I
in
)
1.5 Reference
selection
0—13
13 = Panel reference r1
5
1.6 Jog speed
reference
f
min
—f
max
0.1 Hz 5 Hz 6
1.7 Current limit 0.1—
2.5 x I
nSV9
0.1 A 1.5 x
I
nSV9
Output current limit [A] of the unit 6
1.8 V/Hz ratio selection 0—2 1 0 0 = Linear
1 = Squared
2 = Programmable V/Hz ratio
7
1.9 V/Hz optimization 0—1 1 0 0 = None
1 = Automatic torque boost
8
1.10 Nominal voltage of
the motor
180—690 1 V 230 V
380 V
480 V
575 V
Voltage code 2
Voltage code 4
Voltage code 5
Voltage code 6
8
1.11 Nominal frequency
of the motor
30—500 Hz 1 Hz 60 Hz f
n
on the rating plate of the motor 8
1.12 Nominal speed of
the motor
1—20000 rpm 1 rpm 1440
rpm
n
n
on the rating plate of the motor 8
1.13 Nominal current of
the motor
2.5 x I
nSV9
0.1 A I
nSV9
I
n
on the rating plate of the motor 8
1.14 Supply voltage 180—250
380—440
380—500
525—690
230 V
380 V
480 V
575 V
Voltage code 2
Voltage code 4
Voltage code 5
Voltage code 6
8
1.15 Parameter conceal 0—1 1 0 Visibility of the parameters:
0 = All parameter groups visible
1 = Only group 1 is visible
8
1.16 Parameter value
lock
0—1 1 0 Disables parameter changes:
0 = Changes enabled
1 = Changes disabled
8
* If 1.2 >motor synchr. speed, check suitability for motor and drive system.
Note! =
Parameter value can be changed only when the frequency converter is stopped.
Table 5-1 Group 1 Basic Parameters.