9
Reference Manual
00809-0100-4853, Rev AB
Configuration
January 2017
Configuration
2.3.5 Sending a flow configuration to the transmitter
Select the Send button to download the mass flow configuration file to the transmitter. Sending the
mass flow configuration file will overwrite the existing configuration in the transmitter. Engineering
Assistant will put the Mass Flow Transducer Block out of service when sending the mass flow
configuration.
1. Select the Send button. A confirmation message will display.
2. At the end of the download, choose which mode to put the Mass Flow Transducer Block into, and then
select Continue.
2.3.6 Mass flow test calculation
The mass flow test calculation method allows the user to verify the flow configuration of the Rosemount
3051SMV by entering expected values for the differential pressure, absolute pressure, and process
temperature variables. Test calculation units are always in inH
2
O @ 68 °F for differential pressure, psi for
static pressure and °F for temperature.
To perform a test calculation, select Actions > Methods > Methods > Mass Flow Test Calculation and follow
the on-screen prompts.
Note
The device must be in Automatic Mode in order to successfully perform a mass flow test calculation. If the
resource block is not in automatic mode, the test calculation method will still run, but the method will
report the last live values, rather than the test calculation outputs.