Specifications and Reference Data
January 2017
Reference Manual
00809-0100-4853, Rev AB
Specifications and Reference Data
64
A.3 Ordering information
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment.
Table A-6. Rosemount 3051SMV HART
®
and Fieldbus Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to
additional delivery lead time.
Model Transmitter type
3051SMV Scalable multivariable transmitter
Performance class
(1)
Measurement Types 1 and 2
3
(2)
Ultra for Flow: 0.04% reading DP accuracy, 200:1 rangedown,15-year stability, 15-year limited warranty ★
5 Classic MV: 0.04% span DP accuracy, 100:1 rangedown, 15-year stability ★
Measurement Types 3 and 4
1 Ultra: 0.025% span DP accuracy, 200:1 rangedown, 15-year stability, 15-year limited warranty ★
2 Classic: 0.035% span DP accuracy, 150:1 rangedown, 15-year stability ★
3
(2)
Ultra for Flow: 0.04% reading DP accuracy, 200:1 rangedown,15-year stability, 15-year limited warranty ★
Multivariable type
M Measurement with fully compensated mass and energy
(3)
flow calculations ★
P Measurement of process variables only (no flow calculations) ★
Measurement type
1 Differential pressure, static pressure, and temperature ★
2 Differential pressure and static pressure ★
3 Differential pressure and temperature ★
4 Differential pressure ★
Differential pressure range
(4)
0
(5)
–3 to 3 inH
2
O (–7,46 to 7,46 mbar) ★
1 –25 to 25 inH
2
O (–62,16 to 62,16 mbar) ★
2 –250 to 250 inH
2
O (–621,60 to 621,60 mbar) ★
3 –1000 to 1000 inH
2
O (–2,48 to 2,48 bar) ★
4
–150 to 150 psi (–10,34 to 10,34 bar) for measurement types 1 and 2;
–300 to 300 psi (–20,68 to 20,68 bar) for measurement types 3 and 4
★
5 –2000 to 2000 psi (–137,89 to 137,89 bar) ★
Static pressure type
N
(6)
None ★
A Absolute ★
G Gage ★
Static pressure range Absolute Gage
N
(6)
None N/A N/A ★
3 Range 3 0.5 to 800 psia (0,03 to 55,15 bar) –14.2 to 800 psig (–0,98 to 55,15 bar) ★
4
(7)
Range 4 0.5 to 3626 psia (0,03 to 250,00 bar) –14.2 to 3626 psig (–0,98 to 250,00 bar) ★