Emerson FB2200 Flow Computer Instruction Manual
D301784X012
March 2019
Service and Troubleshooting 93
5.3 Switch and Buttons
A momentary switch and two push buttons on the HMI module provide troubleshooting options
for the flow computer.
Figure 5-3. Switch and Buttons
DANGER
EXPLOSION HAZARD: Never open the enclosure in a hazardous location. Opening the enclosure in
a hazardous location could result in an explosion.
Table 5-3. Switch and Buttons
Button Name
Purpose
Procedure
SYSTEM RESET
Resets Power. This momentary
switch Interrupts power to the
flow computer to reset it. Used if
system powered on but non-
functional; this attempts a reboot.
Move the SYSTEM RESET switch either
up or down. Unit powers off and then
restarts.
A
Clears memory (SRAM). The
SRAM memory holds current data
values and pending alarm
messages. If unit has unexpectedly
stopped operating, you can
depress this button on power- up
to clear that information from
memory (hard reset). Try this if a
SYSTEM RESET alone does not
work.
1. Press and hold the A button.
While continuing to hold the A button,
move the SYSTEM RESET switch either
up or down to initiate a reset.
Release the A button. The system clears
SRAM during the power up sequence.

Table of Contents

Other manuals for Emerson ControlWave Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson ControlWave Series and is the answer not in the manual?

Emerson ControlWave Series Specifications

General IconGeneral
BrandEmerson
ModelControlWave Series
CategoryDesktop
LanguageEnglish

Related product manuals