EasyManuals Logo
Home>Emerson>Controller>Fisher FIELDVUE DVC6000f

Emerson Fisher FIELDVUE DVC6000f User Manual

Emerson Fisher FIELDVUE DVC6000f
384 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
DVC6000f Digital Valve Controllers
December 2009
4-46
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
Basic Setup
BASIC_SETUP
42
Actuator Style
ACTUATOR_STYLE
42.1 RW
MAN
OOS
1=Spring & Diaphragm
2=Piston-Dbl w/o Spring
3=Piston-Dbl w/Spring
4=Piston Sgl w/Spring
1=Spring &
Diaphragm
SETUP Data Type: Enum (Uint8)
Zero Power Condition
ZERO_PWR_COND
42.2 RW
MAN
OOS
1=Valve Closed
2=Valve Open
1=Valve Closed SETUP
Data Type: (Uint8)
Enum Identifies whether the valve
is open or closed when instrument
power is lost.
Travel Sensor Motion
TRAVEL_SEN_MOTION
42.3 RW
MAN
OOS
1=Counter Clockwise
2=Clockwise
1=Counter
Clockwise
SETUP Data Type: Enum (Uint8)
Feedback Connection
FEEDBACK_CONN
42.4 RW
MAN
OOS
1=RShaft Pot
2=SStem Roller Pot
3=SStem Pot
3=SStem Pot SETUP Data Type: Enum (Uint8)
Relay Type
RELAY_TYPE
42.5 RW
MAN
OOS
1=Relay A or C--Double
or Single Direct
2=Relay B--Single
Reverse
5=Relay C-Special App.
--Single Direct
6=Relay B-Special App.
--Single Reverse
9=Lo-Bleed Relay A or
C--Double or Single
Direct
10=Lo-Bleed Relay B--
Single Reverse
13=Lo-Bleed Relay
C-Special App.--Single
Direct
10=Lo-Bleed Relay
B-Special App.-Single
Reverse
=Relay A or
C--Double or
Single Direct
SETUP Data Type: Enum (Uint8)
Maximum Supply Pressure
MAX_SUPP_PRESS
42.6 RW
MAN
OOS
> 0, < = 150 35 psig SETUP Data Type: Float
Pressure Range Hi
PRESS_RANGE_HI
42.7 RW
MAN
OOS
> 0, < = 150 15.0 psig SETUP
Data Type: Float
Defines pressure corresponding to
max pressure in pressure control
mode.
Pressure Range Lo
PRESS_RANGE_LO
42.8 RW
MAN
OOS
> = 0, < = 150 3.0 psig SETUP
Data Type: Float
Defines pressure corresponding to
minimum pressure in pressure
control mode.
Travel Calibration Trigger
TVL_CAL_TRIGGER
42.9 RW
MAN
OOS
1 = Aux Term ignored 1 SETUP Not available in the DVC6000f
Travel Tuning Set
TVL_TUNING_SET
42.10 RW
MAN
OOS
1=B, 2= C, ...12=M
23=X
2=C SETUP
Data Type: Enum (Uint8)
Letter (B through M or X)
Pressure Tuning Set
PRESS_TUNING_SET
42.11 RW
MAN
OOS
1=B, 2=C, ...12= M
23=X
2=C SETUP
Data Type: Enum (Uint8)
Letter (B through M or X)
Continued
4

Table of Contents