Installation
December 2009
2-21
24/48 VDC
110/220 VAC, etc.
Port A
FOUNDATION FIELDBUS
H1 SEGMENT
Port B
SUPPLY PRESSURE
MONITORING LINE
CONTROL LINE
DVC6000f DIGITAL VALVE
CONTROLLER WITH RELAY C
SPRING RETURN ACTUATOR
E1048
NOTES:
1/4-18 NPT X 3/8 OD TUBING
ELECTRICAL WIRING
Figure 2-18. Pneumatic Hookup for Solenoid Testing
the solenoid valve and the actuator, as shown in figure
2-18. When single-acting, direct relay C is installed,
the “unused” output port is port B. When single-acting,
reverse relay B is used, the unused port is port A.
Note
Solenoid valve testing is only available
for instrument level PD.
Note
This application is called “special
application” in the Device Setup relay
selection.
This configuration is not possible with
a double-acting actuator or when
using relay A in single-acting mode.
Vent Connection
WARNING
This unit vents the supply medium
into the surrounding atmosphere.
When installing this unit in a
non-hazardous (non-classified)
location in a confined area, with
natural gas as the supply medium,
you must remotely vent this unit to a
safe location. Failure to do so could
result in personal injury or property
damage from fire or explosion, and
area re-classification.
When installing this unit in a
hazardous (classified) location remote
venting of the unit may be required,
depending upon the area
classification, and as specified by the
requirements of local, regional, and
federal codes, rules, and regulations.
Failure to do so when necessary
could result in personal injury or
property damage from fire or
explosion, and area re-classification.
Vent line piping should comply with
local and regional codes and should
be as short as possible with adequate
insider diameter and few bends to
reduce case pressure buildup.
In addition to remote venting of the
unit, ensure that all caps and covers are
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals