EasyManuals Logo

Emerson Fisher FIELDVUE DVC6000f User Manual

Emerson Fisher FIELDVUE DVC6000f
384 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #225 background image
DI Function Block
December 2009
4-165
When SIMULATE_D [9] is enabled, the Simulate
Active bit of the BLOCK_ERR [6] parameter is set
(refer to the Block Errors description). When the
simulate jumper is installed, the Simulate Jumper bit of
the transducer block parameter SELFTEST_STATUS
[78] is set.
Application Information
Figure 4-33 compares the operation of a standard
discrete input to a proximity discrete input. With the
standard discrete input, the discrete input changes
state when the valve position passes a configurable
trip point. This can be used to indicate if the valve
position is above or below the trip point.
With the proximity discrete input a configurable band
can be established about a central point. Whenever
the valve position enters this configurable band, the
discrete input changes state. A proximity discrete input
is useful for applications which require knowing the
location of the valve when the valve is not near 0% or
100%.
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals