DVC6000f Digital Valve Controllers
December 2009
4-60
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
Self Test Status
SELFTEST_STATUS
78 RO N/A 0:
2: Integrator Limited Low
3: Integrator Limited
High
4: Travel Sensor Span
Error
5: MLFB Error
7: Travel Sensor High
Error
8: Travel Sensor Low
Error
9: Pressure Sensor B
10: Pressure Sensor A
11: Supply Pressure
Sensor
13: IOP Failure
14: Drive Current
15: Simulate Jumper ON
All bits: 0 Data Type: Bit String (2 byte)
0=inactive
1=active
Indicates the status of the
instrument self test.
Integrator Limited Low: Indicates
the integrator reached its limit and
cannot move the valve any further.
High valve friction may cause this
situation.
Integrator Limited High:
Indicates the integrator reached its
limit and cannot move the valve
any further. High valve friction may
cause this situation.
Travel Sensor Span Error:
Indicates that span between the
endpoints of travel are not far
enough apart. This error is reported
during automatic calibration.
MLFB Error: Indicates that the
Minor Loop Feedback sensor gave
a non-valid value during automatic
calibration.
Travel Sensor High Error:
Indicates the travel sensor has
reported a travel position that is
significantly above the normal
operating range, and has failed.
Travel Sensor Low Error:
Indicates the travel sensor has
reported a travel position that is
significantly below the normal
operating range, and has failed.
Pressure B Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
Pressure A Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
Supply Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
IOP Failure: Indicates the I/O
processor has failed.
Drive Current: Indicates that the
Drive Current has exceeded the
Drive Current Alert Point for more
than the Drive Current Alert Time.
Simulate Jumper ON: Indicates
the simulate jumper is connected to
the DVC6000f between the two
AUX terminals.
Health Index
HEALTH_INDEX
79 RO N/A 0 100 100 N/A
Data Type: Uint8
Represents overall health of
device. 100 is perfect, 0 is
completely bad. Settings for
DVC6000f will range from 10 to
100.
Reserved A
RESERVED_A
80 RW ALL N/A SETUP
Data Type: Array, 118 x Unit8
Reserved
Reserved AI
RESERVED_AI
81 RW ALL 0 SETUP
Data Type: Uint16
Reserved
Continued
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals