DVC6000f Digital Valve Controllers
December 2009
4-62
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
SPEC_SHEET_ACT
85
Actuator Size
ACTUATOR SIZE
85.1 RW ALL NULL ALL Data Type: Visible String
Effective Area
EFFECTIVE AREA
85.2 RW ALL 0.00 ALL Data Type: Float
Air
AIR
85.3 RW ALL
1=open
2=close
0 ALL Data Type: Enum (Uint8)
Lower Bench Set
LOWER_BENCH_SET
85.4 RW ALL 0.00 ALL Data Type: Float
Upper Bench Set
UPPER_BENCH_SET
85.5 RW ALL 0.00 ALL Data Type: Float
Nominal Supply Pressure
NOMINAL_SUPPLY_PRESSURE
85.6 RW ALL 0.00 ALL Data Type: Float
Spring Rate
SPRING_RATE
85.7 RW ALL 0.00 ALL Data Type: Float
Stroking Time Open
STROKING_TIME_OPEN
85.8 RW ALL 0.00 ALL
Data Type: Float
Seconds
Stroking Time Close
STROKING_TIME_CLOSE
85.9 RW ALL 0.00 ALL
Data Type: Float
Seconds
Lever Style
LEVER_STYLE
85.10 RW ALL
1=Pivot Point
2=Rack & Pinion
0 ALL Data Type: Enum (Uint8)
Lever Arm Length
MOMENT_ARM
85.11 RW ALL 0.00 ALL Data Type: Float
DEVICE_RECORD
86
These parameters can only reset
through VL/DD.
Temperature Maximum
TEMP_MAX
86.1 RO N/A −9999.99 N/A
Data Type: Float
Highest temperature recorded
Temperature Maximum Time
TEMP_MAX_TIME
86.2 RO N/A Zero time N/A Data Type: Time Value
Temperature Minimum
TEMP_MIN
86.3 RO N/A 9999.99 N/A
Data Type: Float
Lowest temperature recorded
Temperature Minimum Time
TEMP_MIN_TIME
86.4 RO N/A Zero time N/A Data Type: Time Value
Supply Pressure Maximum
SUPP_PRESS_MAX
86.5 RO N/A 0.0 N/A
Data Type: Float
Highest supply pressure recorded
Supply Pressure Maximum Time
SUPP_PRESS_MAX_TIME
86.6 RO N/A Zero time N/A Data Type: Time Value
Supply Pressure Minimum
SUPP_PRESS_MIN
86.7 RO N/A 9999.99 N/A
Data Type: Float
Lowest supply pressure recorded
Supply Pressure Minimum Time
SUPP_PRESS_MIN_TIME
86.8 RO N/A Zero time N/A Data Type: Time Value
Comm Error Count
COMM_ERROR_COUNT
86.9 RW N/A 0 SETUP Not used by the DVC6000f
Protection
PROTECTION
87 RW ALL
1=None
2=Calibration
3=Setup & Calibration
4=All
2=Calibration NONE
Data Type: Enum
Write lock enable/disable. If setting
is at or above a parameters
protection level then that parameter
is read-only.
PERF_DIAG
88
PD Run
PD_COMMAND
88.1 RW
AUTO
MAN
1=PD On
2=PD Off
1=PD On NONE
Data Type: Enum
Controls whether PD will run or not.
PD Status
PD_STATUS
88.2 RO ALL
1=Not Running
2=Running
NONE
Data Type: Enum
Status of performance diagnostics.
PD Configuration
PD_CONFIG
88.3 RW ALL 0 NONE
Data Type: Bit String
Bit string for configuring PD setup
and options.
PD Extra
PD_EXTRA
88.4 RW ALL 0 NONE
Data Type: Uint32
Extra 32 bit integer for sending
values to PD.
−Continued−
4