SUPPLEMENTARY OPERATING MANUAL 2
2-
11
05-19-06 CDP-01 Figure Sheet 1-900
Start-up / Sensor Drive Polarity
Sensor Servo-Center Polarity
Select Drive 3 by pressing key 20.
Press the Servo Center key. Verify that the sensor
moves to the desired end for retract.
If the sensor moves the wrong direction, press the
Manual key and change the Servo Center polarity.
Reference: CDP-01 Reference Manual, section
“Servo Center Polarity”.
Sensor Automatic Polarity
Select Drive 3 by pressing key 20.
Press the Sensor key repeatedly until LED 10 is lit.
Press the Automatic key. Verify that the sensor
moves to the edge of the web.
If the sensor moves the wrong direction, press the
Manual key and change the guide polarity
Reference: CDP-01 Reference Manual, section
“Changing The Guide Direction”.