3 SETUP AND USE
g
GE Power Management
42
Table 3-3 SETPOINTS
3$*( ,1)250$7,21 /,1( 5$1*( 0$18$/ 5()
1
PAGE 1: SETPOINTS VALUES
MOTOR AMPS SETPOINTS
1
PHASE CT RATIO
SECONDARY = X AMP
:1 or :5 3.7
1
PHASE CT RATIO
CT RATIO = XXXX:x
20-1500 (increments of 1) 3.7
1
MOTOR FULL LOAD CURRENT
FLC= XXXX AMPS
10-1500 amps (increments of 1) 3.7
1
ACCEL.TIME= XXX.X SECONDS
Consult motor data sheet
0.5-125.0 or OFF (increments of 0.5) 3.8
1
STARTS/HOUR= X
Consult motor data sheet
1-5 starts or OFF (increments of 1) 3.9
1
UNBALANCE ALARM LEVEL
U/B ALARM= XX PERCENT
4-30 % or OFF (increments of 1) 3.10
1
U/B ALARM TIME DELAY
TIME DELAY = XXX SEC
3-255 seconds (increments of 1) 3.10
1
UNBALANCE TRIP LEVEL
U/B TRIP= XX PERCENT
4-30 % or OFF (increments of 1) 3.10
1
U/B TRIP TIME DELAY
U/B DELAY= XXX SECONDS
3-255 seconds (increments of 1) 3.10
1
G/F CT RATIO :5 ? XXX
(NO indicates 2000:1)
YES (5 amp secondary) or NO (2000:1) 3.11
1
G/F CT RATIO
G/F CT = XXX:5
50-250 (increments of 50)
(Not seen if ratio is 2000:1)
3.11
1
GROUND FAULT ALARM LEVEL
G/F ALARM= XXX AMPS
2000:1 CT: 1.0-10.0 amps or OFF (steps of 1.0)
5 A secondary CT: 10-100% of primary amps or
OFF (increments of 10%)
3.11
1
G/F ALARM TIME DELAY
TIME DELAY = XXX SEC
1-255 seconds (increments of 1) 3.11
1
GROUND FAULT TRIP LEVEL
G/F TRIP = XXX AMPS
2000:1 CT: 1.0-10.0 A or OFF (steps of 1.0)
5 A secondary CT: 10-100% of primary amps or
OFF (increments of 10% )
3.11