GE Power Management
66
Table 3-5 Standard Overload Curve Trip Times (in seconds)
MULTILIN STANDARD CURVE NUMBERSOverload
Level
1 2 3 4
*
5 6 7 8
1.05 853 1707 2560 3414 5975 7682 10243 12804
1.10 416 833 1250 1666 2916 3750 5000 6250
1.20 198 397 596 795 1392 1789 2386 2982
1.30 126 253 380 507 887 1141 1521 1902
1.40 91 182 273 364 638 820 1093 1367
1.50 70 140 210 280 490 630 840 1050
1.75 42 84 127 169 297 381 509 636
2.00 29 58 87 116 204 262 350 437
2.25 21 43 64 86 150 193 258 323
2.50 16 33 50 66 116 150 200 250
2.75 13 26 39 53 93 119 159 199
3.00 10 21 32 43 76 98 131 164
3.50 7 152331546993116
4.00 5 11172340526987
4.50 4 9 13 18 31 40 54 68
5.00 3 7 10 14 25 32 43 54
5.50 2 5 8 11 20 26 35 44
6.00 2 5 7 10 17 22 30 37
6.50 2 4 6 8 14 19 25 31
7.00 1 3 5 7 12 16 21 27
7.50 1 3 4 6 11 14 19 23
8.00 1 2 4 5 9 12 16 20
*
Factory preset value