3300/16 Dual Vibration Monitor Operation Manual
12
7. Read Setpoint Values
7.1 Read Alert Setpoints
Press the ALERT switch to read the Alert
setpoint for both channel A and B on the
meter scale.
This monitor shows Alert setpoints of the
6.0 mil for channel A and 5.2 mil for
channel B.
Press the GAP and ALERT switches
simultaneously to read the Gap Alert
setpoint windows for both channel A
and B on the meter scale using the
center scale.
This monitor shows over and under Alert
setpoints of 18 mil toward and 9 mil
away for channel A and 15 mil toward
and 5 mil away from channel B.