Telephone Line Monitor
The NX-6 has a Telephone Line Monitor that monitors the volta
g
e and current of the telephone line for a detection of a
faulted phone line. This condition can also be reported to the central station. If the report is enabled, only the
Telephone Line Restore will be reported. (Loc. 37, 39, and 40, pg. 19-20)
Temporal Siren Disable
NOTE: This feature must NOT be disabled for UL
installations.
If disabled, the Fire siren will be steady and Fire Volta
g
e Out will be the same as Bur
g
lary (continuous). If enabled, the
Fire siren will be temporal. (Loc. 37, pg. 19)
Tone Sniff Answering Machine Defeat
If enabled, only one call is required to defeat the answerin
g
machine. To use this feature you must have a Hayes 1200
Smart Modem. From the computer, call the panel as normal. When the answerin
g
machine answers, the panel will
hear the tones from the modem and seize the phone line for a download. (Loc. 21, pg. 16)
Two Call Answering Machine Defeat
If enabled, to defeat an answering machine, two telephone calls must be made to the premises. On the first call, let the
phone ring one or two times. The control panel will detect these rings and start a 45-second timer, durin
g
which, the
control panel will answer the next call on the first ring. This is not recommended for commercial applications.
(Loc. 21, pg. 16)
Walk-Test Mode
If enabled, entering [r] [Chime] followed by a user code will allow a walk-
through zone test where all zones become
silent and local (non-reportin
g
). Each time a zone is faulted, the zone li
g
ht on the LED keypad will illuminate and the
chime will sound. The number of the faul
ted zone(s) will be displayed on the LCD keypad. It will also be entered into
alarm memory and the internal log. To exit at any time during this mode, enter a user code. Otherwise the AWalk-
Test
Mode@ will automatically exit after 15 minutes. (Loc. 41, pg. 21)
Wireless Sensor Missing/Low Battery
The NX-6 will send a report to the central station when a wireless sensor has detected a low battery or has not reported
to the receiver. The "Service" LED will illuminate when either condition exists. (Loc. 37, pg. 19)
Zone Bypassed Sounder Alert
If enabled, the NX-6 will beep the keypad sounder upon arming if a zone is bypassed. (Loc. 23, pg. 17)
Zone Doubling
This feature allows you to use the six zones on the panel as twelve normally closed zones. When this feature is used,
zone seven cannot be a two-wire smoke zone, and European double E.O.L. configuration cannot be used. THIS
FEATURE DOES NOT INCREASE THE TOTAL NUMBER OF AVAILABLE ZONES BEYOND 16 INCLUDING
WIRELESS. Zones 7 - 12 should not programmed as AFire@ Zone Types when Zone Doublin
g
is used. If one of the
twelve zones must be a fire zone, it must be one of Zones 1 to 6. The correspondin
g
upper zone will become
unavailable. For example, if Zone 6 is a fire zone, then Zone 12 will not be available. (Loc. 37, pg. 19)
Zone Types
The NX-6 has 20 pro
g
rammable Zone Types that determine how each zone will function and report. The default Zone
Types are listed on page 18. (Loc. 110-149, pg. 28)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NetworX NX-6 and is the answer not in the manual?

GE NetworX NX-6 Specifications

Operating Power IconOperating Power
operating power16.5 VAC 25, 40, or 50 VA Transformer
auxiliary power with 25 VA transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA transformer12 VDC Regulated 1 AMP
Loop Specifications IconLoop Specifications
loop resistance for standard loop300 Ohms Maximum
loop resistance for 2-wire smokes30 Ohms Maximum
loop response500mS
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
LED Keypad Specifications IconLED Keypad Specifications
led keypad current draw130 mA max.
led keypad dimensions width6.4"
led keypad dimensions height4.0"
led keypad dimensions depth1.1"
NX-148E LCD Keypad Specifications IconNX-148E LCD Keypad Specifications
nx-148e lcd keypad current draw110 mA max.
nx-148e lcd keypad dimensions width6.4"
nx-148e lcd keypad dimensions height5.3"
nx-148e lcd keypad dimensions depth1.0"
Enclosure and Shipping IconEnclosure and Shipping
metal enclosure dimension width11.25"
metal enclosure dimension height11.25"
metal enclosure dimension depth3.50"
shipping weight9 lbs.