12
NX-6V2 Control
L 3 DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE 1 2 ........... numerical
Segment 1- Dial attempts: Location 3, Segment 1 is used to enter the number of dial attempts (1 to 15 Attempts) the communicator
will make to Phone 1 before ending the notification process. Factory default is "8" and the communicator will make eight (8) attempts
to the first number.
Segment 2- Phone 1 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-6V2 to make the designated
number of attempts to Phone 2 before setting the "Fail To Communicate" condition and stop reporting. Programming a "1" in this
segment will cause the NX-6V2 to stop trying to communicate after the designated number of attempts have been made to Phone 1. If
a "2" is programmed in this segment, it will cause the NX-6V2 to make the dial attempts in increments of two. The first two attempts will
be made to Phone 1, the next two attempts to Phone 2, then repeating until the total number of attempts designated in Segment 1 is
completed.
REPORTING EVENTS TO PHONE NUMBER 1
Phone 1 has two programming locations that are used to select which events are reported to this phone number. Location 4 is used to
select which events are reported to Phone 1. Location 5 is used to select which partitions are reported to Phone 1. If dual or split
reporting is not desired, location 4 should be used to select all events to Phone 1 and location 5 should be left at the factory default of
"0". If dual or split reporting is desired, and the split is based on the event type (such as alarm, open/close, etc.), location 4 should be
used to select only those events that should be reported to Phone 1 and location 5 should be left at the factory default of "0". If dual or
split reporting is desired, and the split is based on partition, location 4 should be programmed as a "0" and location 5 should be used to
select those partitions that should be reported to Phone 1. If no events should be reported to Phone 1, both locations should be
programmed as "0" (disabling all options).
4 EVENTS REPORTED TO PHONE 1 2 ............ feature select
Segment 1:
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming, Download complete.
Segment 2:
1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Overcurrent, Ground Fault, and Restore for both.
3 = Wireless Sensor Missing and Restore.
4 = Wireless Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Zone Activity Monitor.
8 = Reserved.
5 PARTITIONS REPORTED TO PHONE 1 1 ............ feature select
Location 5 is used when events to be reported to a phone number are based upon the partition regardless of the event. If this location
is used, location 4 should be programmed as "0".
Segment 1:
1 = Partition 1 2 = Partition 2
L 6 PROGRAMMING PHONE 2 20 .......... numerical
Phone 2 is programmed in location 6. A "14" indicates the end of the phone number. Delays of four seconds can be programmed at
any point in the phone number by programming a "13" in the appropriate segment. If tone dialing is desired, program a "15" in the
segment where tone dialing should begin. If the entire number should be tone dialing, program a "15" in the first segment. Program an
A11" for a Ar@, and a A12" for a A#@. Caution: A call-waiting cancel on a non- call waiting line will prevent successful connection to the
central station.
L 7 ACCOUNT CODE FOR PHONE 2 6 ............ numerical
The account code sent when Phone 2 is dialed is programmed in location 7. Program a A10" in the segment immediately after the last
digit of the account code. If the account code is 6 digits long, program all 6 segments. If this location is left unprogrammed, account
code 1 will be used when the second phone number is dialed.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NetworX NX-6V2 and is the answer not in the manual?

GE NetworX NX-6V2 Specifications

Power IconPower
operating power16.5 VAC 40, or 50 VA Transformer
auxiliary power with 25 VA Transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA Transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320E Power Supply12 VDC Regulated 2 AMPS + Control Panel Power
Loop Specifications IconLoop Specifications
loop resistance standard loop300 Ohms Maximum
loop resistance 2-wire smokes30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
Keypad Specifications IconKeypad Specifications
LED keypad current draw130 mA max.
LED keypad zones normal without sounder55 mA
LED keypad dimensions6.4" Wide, 4.0" High, 1.1" Deep
NX148E LCD keypad current draw110 mA max.
NX148E LCD keypad without sounder75 mA
NX148E LCD keypad dimensions6.4" Wide, 5.3" High, 1.0" Deep
Dimensions and Weight IconDimensions and Weight
metal enclosure dimension11.25" Wide, 11.25" High, 3.50" Deep
shipping weight9 lbs.