NX-6V2 Control
V. TERMINAL DESCRIPTIONS
TERMINAL DESCRIPTION
R1
House Telephone Ring (Grey).
R
Telephone Ring (Red).
T
Telephone Tip (Green).
T1
House Telephone Tip (Brown).
EARTH
Earth Ground. Connect to a cold water pipe or a 6 to 10 foot driven rod.
AC
AC input. Connect to a 16.5V 40 or 50 VA Class ll U.L. approved transformer.
BELL + & BELL
-
If used as a siren output (default), the speaker rating should be 15 watt at 8 or 16 ohm, or 30/40 watt at 4, 8,
or 16 ohms. If voltage output is selected in location 37, this output becomes voltage output, 12VDC, 1 Amp
maximum load. NOTE: A 3.3K resistor may be required across the bell terminals when a 12 VDC
siren is used. If no resistor is used, you may experience voltage leakage into the siren, which will
cause these devices to output a small signal.
DATA
Connect to the data terminal on the keypads and the expanders. Maximum number of devices is 16 keypads
+ 3 other devices. See AMaximum Wire Run@ chart below.
COM
Connect to the Common terminal on the keypads and the expanders.
POS
Connect to the POS terminal on the keypads and the expanders. Individually, this terminal is limited to 1
Amp. Combined, this terminal and AUX PWR + are limited to 2 amps total current.
COM
Connect negative wire of powered devices such as motion detectors and smoke detectors.
AUX +
Connect positive wire of all powered devices except smoke detectors and keypads. Individually, this terminal
is limited to 1 Amp. Combined, this terminal and KP POS are limited to 2 amps total current.
ZONE 6
Connect to one side of zone 6 loop. Connect the other side to com terminal. Open or short causes alarm.
Only Zone 6 can used for a two-wire smoke detector, connected with a 680 E.O.L. resistor. Refer to the
wiring diagram. Program location 37, segment 6, option 1. Only zone 6 can be a two-wire zone.
COM
Common (-) terminal for zones 5 & 6. (See the wiring diagram for examples.)
ZONE 5
Connect to one side of zone 5 loop. Connect the other side to COM terminal. Open or short causes alarm.
ZONES 1- 4
Connect as described for zones 5 & 6.
AUXOUT 4
(SMOKE +)
Smoke detector power 12VDC (for those jurisdictions which allow the Priority zone to be used with smoke
detectors.) Current limited to 250mA when output is positive and 250FA when output is negative. This output
defaults to Smoke Power, but can be re-configured. Zone 7 may be used for a 2-wire smoke detector
using a 680 ohm EOL resistor.
AUXOUT 1- 3
Connect negative lead of low current device [relay, LED (install 1K resistor in series with LED), etc.].
Connect positive lead of device to COM. Current is limited to 250mA when output is negative, and 250FA
when output is positive.
NETWORX KEYPAD MAXIMUM WIRE RUN
(Note: These numbers are for one keypad at the end of the wire. When connecting more than one keypad to the end of the wire, a
higher gauge wire will be required.)
WHEN CONNECTED TO NX-6V2 WHEN CONNECTED TO NX320-E
Length in feet Wire Gauge Wire Gauge
250 24 22
500 20 18
1000 18 16
1500 16 14
2500 14 12

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NetworX NX-6V2 and is the answer not in the manual?

GE NetworX NX-6V2 Specifications

Power IconPower
operating power16.5 VAC 40, or 50 VA Transformer
auxiliary power with 25 VA Transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA Transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320E Power Supply12 VDC Regulated 2 AMPS + Control Panel Power
Loop Specifications IconLoop Specifications
loop resistance standard loop300 Ohms Maximum
loop resistance 2-wire smokes30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
Keypad Specifications IconKeypad Specifications
LED keypad current draw130 mA max.
LED keypad zones normal without sounder55 mA
LED keypad dimensions6.4" Wide, 4.0" High, 1.1" Deep
NX148E LCD keypad current draw110 mA max.
NX148E LCD keypad without sounder75 mA
NX148E LCD keypad dimensions6.4" Wide, 5.3" High, 1.0" Deep
Dimensions and Weight IconDimensions and Weight
metal enclosure dimension11.25" Wide, 11.25" High, 3.50" Deep
shipping weight9 lbs.