XXIV. ANSI / SIA CP-01 REQUIREMENTS
To meet SIA CP-01 requirements –
Minimum System Requirements: 1 control panel; 2 keypads (or 1 keypad per partition for multi-partitioned systems)
Remote arming shall NOT be enabled in SIA classified installations.
Off-premise transmission must be in the SIA format.
The Abort window and Entry Delay must not exceed 1 minute.
CAUTION – A call waiting cancel on a non-call waiting line will prevent successful connection to the central station.
CP-01 Feature
Description
Feature Description
as shown in manual
Program
Loc
Seg / Opt
Factory
Default
CP-01 Required
Setting
Exit Time Exit 1 Delay
24
2
60
45 – 240 sec.
Exit 2 Delay
24
4
60
45 – 240 sec.
Progress Annuncation / Disable
– for Silent Exit
Silent Keypad Option
9 3
2
All annunciators enabled Allowed
(individual keypads may be disabled)
Exit Time Restart This feature is non-programmable in the panel. Enabled
Auto Stay Arm on Unvacated Premises Auto Bypass
23
1 / 3
Enabled Enabled
Exit Time and Progress
Annunciation / Disable
– for Remote Arm
This feature is non-programmable in the panel. -- Exit time and progress are always enabled. Enabled (may be disabled for remote arming)
Entry Delay(s) Entry 1 Delay
24
1
30 30 – 240 sec.
Entry 2 Delay
24
3
30 30 – 240 sec.
Abort Window
– for Non-Fire Zones
Dialer Delay
40
8
30 Enabled
(may be disabled by zone/ zone type)
Abort Window Time
– for Non-Fire Zones
Dialer Delay
40
8
30 15 – 45 sec.
NOTE:
Combined
Abort window
and Entry
Delay must
not exceed 1
minute.
Abort Annunciation This feature is non-programmable in the panel. -- Flashing Cancel LED goes off when disarming. Enabled
Cancel Annunciation Cancel
23
3 / 6
Enabled Enabled
Duress Feature Duress
44
Disabled
Disabled
Cross Zoning
2 Trips on Cross Zone
37
5 / 4
Disabled
Required
Keypad sounds on Cross Zone trip
39
5
Disabled
Zone Type Characteristic
111
3 / 4
Disabled
Programmable Cross Zoning Time
Cross Zone Time
40
6
5 minutes
Allowed
Swinger Shutdown Swinger Shutdown Count
38
n/a
Enabled for 1 trip For all non-fire zones, shut down at 1–2 trips
Swinger Shutdown Disable Swinger Shutdown Count
38
n/a
Enabled for 1 trip Allowed
Fire Alarm Verification Fire Alarm Verification Time
40
9
Disabled Required (depends on panel & sensors)
Call Waiting Cancel Must be programmed as part of the
phone number
0
n/a
n/a Required (depends on user phone line)
Default Changes (from prior versions):
Recent Closing
23
3 / 7
Enabled
Exit Error
23
3 / 8
Enabled
Power Up Delay
40
3
60 sec.
IMPORTANT NOTE:
UL requirements take
priority over SIA
requirements.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NetworX NX-6V2 and is the answer not in the manual?

GE NetworX NX-6V2 Specifications

Power IconPower
operating power16.5 VAC 40, or 50 VA Transformer
auxiliary power with 25 VA Transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA Transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320E Power Supply12 VDC Regulated 2 AMPS + Control Panel Power
Loop Specifications IconLoop Specifications
loop resistance standard loop300 Ohms Maximum
loop resistance 2-wire smokes30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
Keypad Specifications IconKeypad Specifications
LED keypad current draw130 mA max.
LED keypad zones normal without sounder55 mA
LED keypad dimensions6.4" Wide, 4.0" High, 1.1" Deep
NX148E LCD keypad current draw110 mA max.
NX148E LCD keypad without sounder75 mA
NX148E LCD keypad dimensions6.4" Wide, 5.3" High, 1.0" Deep
Dimensions and Weight IconDimensions and Weight
metal enclosure dimension11.25" Wide, 11.25" High, 3.50" Deep
shipping weight9 lbs.