4 NX-
I. GENERAL DESCRIPTION
The NX-320E is a microprocessor controlled remote power supply module for the NX-8 / NX-8E / NX-8-CF control
panel. This power supply module has three (3) programmable outputs and one (1) dedicated bell output. A
maximum of eight (8) power supply modules can be added to the NetworX control panel for a total output count of
32, of which 24 are programmable and 8 are dedicated bell outputs. These 24 programmable outputs can be used as
auxiliary power, smoke detector power, siren driver power, etc. (see chart on page 11). Each power supply module
has a Tamper terminal that can be used to supervise the metal enclosure. When the power supply module is
connected to the NX-8 / NX-8E / NX-8-CF control panel, the maximum total wire run from the panel to all devices,
including the NX-320E, is 2500 feet. Additionally, the maximum total wire run from the power supply module to all
outgoing devices is 2500 feet.
It is not recommended that multiple power supply modules be connected in series (cascaded).
II. ORDERING INFORMATION
Please refer to the GE Interlogix product catalog for warranty details.
PART # DESCRIPTION
NX-320E Remote Power Supply
NX-8 NX-8 Control Panel only
NX-8-KIT NX-8 Control, NX-108E LED Keypad, & 16.5V 40VA Transformer
NX-8-CF NX-8 Commercial Fire Control Panel only
NX-848-CF-KIT NX-8 Commercial Fire Control Panel in NX-003-CF Enclosure, NX-148ECF
LCD keypad; NX-870E Fire Supervision module; 16.5V 50VA Transformer
NX-216E 16 Zone Expander
NX-408E # 8 Zone Wireless Expansion Module (UL LISTED PART #60-904)
NX-416E # 16 Zone Wireless Expansion Module (UL LISTED PART #60-904)
NX-448E # 48 Zone Wireless Expansion Module (UL LISTED PART #60-904)
NX-508E Eight Output Module
NX-870E Fire Supervision Module
NX-003-CF Commercial Fire Enclosure (Red)
# These wireless devices are UL listed for residential applications only.
III. UNDERWRITERS LABORATORIES INFORMATION
UL365 Police Station Connected Burglar Alarm Units &
Systems
UL985 Household Fire Warning Systems
UL609 Local Burglar Alarm Units & Systems UL1023 Household Burglar Alarm Systems
UL864 Control Units for Fire-Protective Signaling Sytems UL1610 Central Station Burglar Alarm Units
When the NX-320E Remote Power Supply is used as part of a UL Commercial Fire security system:
Unit is compatible with the following devices:
o NX-148E-CF LCD keypad
o NX-216E Zone Expander
o NX-507E Relay Expander
o Wheelock NS-1215W or NS-121575W Siren
A minimum of 18AWG shall be used for all field wiring.
Use a 16.5VAC 50VA / 120V, 60Hz hard-wired transformer (Caddx part #T-0002)