73
10 Technical Parameters
User Manual V1.1-2022-12-20
10.2 Technical Parameter - BT Series
Technical Parameters GW5K-BT GW6K-BT GW8K-BT GW10K-BT
Battery Input Data
Battery Type Li-Ion Li-Ion Li-Ion Li-Ion
Nominal Battery Voltage (V) 500 500 500 500
Battery Voltage Range (V) 180 ~ 600 180 ~ 600 180 ~ 600 180 ~ 600
Max. Continuous Charging Current
(A)
25 25 25 25
Max. Continuous Discharging
Current (A)
25 25 25 25
Max. Charge Power (W) 5,000 6,000 8,000 10,000
Max. Discharge Power (W) 5,000 6,000 8,000 10,000
AC Output Data (On-grid)
Nominal Apparent Power Output to
Utility Grid (VA)
5,000 6,000 8,000 10,000
Max. Apparent Power Output to
Utility Grid (VA)
*1 *6
5,500 6,600 8,800 11,000
Nominal Apparent Power from
Utility Grid (VA)
10,000 12,000 15,000 15,000
Max. Apparent Power from Utility
Grid (VA)
10,000 12,000 15,000 15,000
Nominal Output Voltage (V)
400/380,
3L/N/PE
400/380,
3L/N/PE
400/380,
3L/N/PE
400/380,
3L/N/PE
Nominal AC Grid Frequency (Hz) 50/60 50/60 50/60 50/60
Max. AC Current Output to Utility
Grid (A)
8.5 10.5 13.5 16.5
Max. AC Current From Utility Grid (A) 15.2 18.2 22.7 22.7
Nominal Output Current (A) 7.2 8.7 11.6 14.5
Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion <3% <3% <3% <3%
AC Output Data (Back-up)
Back-up Nominal Apparent Power
(VA)
5,000 6,000 8,000 10,000
Max. Output Apparent Power (VA)
*2
5,000
(10,000
@60sec)
6,000
(12,000
@60sec)
8,000
(15,000
@60sec)
10,000
(15,000
@60sec)
Max. Output Current (A) 8.5 10.5 13.5 16.5