10 Technical Parameters
User Manual V1.3-2023-01-31
50
Technical Data GW25K-MT GW29.9K-MT GW30K-MT GW36K-MT
Input(DC)
Max. Input Power (kW) 32.5 39 39 42.9
Max. Input Voltage (V) 1100
MPPT Operating Voltage
Range (V)
200~950
MPPT Voltage Range at
Nominal Power (V)
510~860
Start-up Voltage (V) 180
Nominal Input Voltage (V) 600
Max. Input Current per
MPPT(A)
30 or 25
[1]
Max. Short Circuit Current
per MPPT (A)
37.5 or 31.3
[1]
Max. Backfeed Current to
The Array (A)
0
Number of MPP Trackers 3
Number of Strings per MPPT 2/2/2
Output(AC)
Nominal Output Power (kW) 25 29.9 30 36
[2]
Nominal Output Apparent
Power (kVA)
25 29.9 30 36
[2]
Max. AC Active Power (kW) 27.5
[3]
29.9 33
[3]
36
Max. AC Apparent Power
(kVA)
27.5
[4]
29.9 33
[4]
36
Nominal Power at 40℃ (kW)
(Only for Brazil)
25 / 30 36
Max Power at 40℃ (Including
AC Overload)(kW) (Only for
Brazil)
25 / 30 36
Nominal Output Voltage (V)
400
*5
, 3L/N/PE
or 3L/PE
Output Voltage Range (V) 320~460
Nominal AC Grid Frequency
(Hz)
50/60

Other manuals for Goodwe SMT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe SMT Series and is the answer not in the manual?

Goodwe SMT Series Specifications

General IconGeneral
BrandGoodwe
ModelSMT Series
CategoryInverter
LanguageEnglish

Related product manuals