EasyManuals Logo
Home>Grant>Boiler>Vortex Series

Grant Vortex Series User Manual

Grant Vortex Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
4.5 PIPEWORK MATERIALS
The Grant Vortex boiler is compatible with both copper and plastic
pipe. Where plastic pipe is used it must be of the oxygen barrier
type and be the correct class (to BS 7291-1) for the application
concerned.
On either sealed or open-vented systems; where plastic pipe is
used a minimum of ONE metre of copper pipe (or as per pipe
manufacturers instructions) MUST be connected between both
the boiler ow and return connections and the plastic pipe.
! NOTE !
Do not connect plastic pipe directly to the boiler.
Grant UK does not accept any responsibility for any damage,
however caused, to plastic piping or ttings.
SEALED SYSTEMS
If plastic pipe is to be used, the installer must check with the
plastic pipe manufacturer that the pipe to be used is suitable for
the temperature and pressures concerned.
Plastic pipe must be Class S to BS 7291-1.
! WARNING !
When plastic pipe is used, the system MUST incorporate
a low pressure switch to shut o󰀨 power to the boiler if
the system pressure drops below 0.2 bar. A suitable low
pressure switch kit is available to purchase from Grant UK
(product code: MPCBS62).
UNDERFLOOR PIPEWORK
Plastic pipe may be used on underoor oor systems where the
plastic pipe is tted after the thermostatic mixing valve. Copper
tube must be used for at least the rst metre of ow and return
primary pipework between the boiler and the underoor mixing/
blending valves.
4.6 CONNECTIONS
4.6.1 FLOW, RETURN AND HOT WATER
CONNECTIONS
Refer to Section 5.
4.6.2 CONDENSATE CONNECTION
Grant Vortex Outdoor Combi boilers are supplied with a factory-
tted condensate trap to provide the required 75 mm water seal
in the condensate discharge pipe from the boiler.
Refer to Section 6 for details of the condensate disposal pipework.
4.6.3 DRAIN COCK
A drain cock is tted at the bottom on the front of the boiler to
allow the heating system to be drained.
There is also a drain cock tted at the bottom on the front of the
primary store.
4.7 PREPARATION FOR
INSTALLATION
1. Carefully remove the packaging from the boiler and remove it
from the transit pallet.
2. Remove the case top panel (four screws) and also the front
and rear panels as required.
3. The ue may exit the boiler from the left, right or rear of the
casing. Carefully press out the pre-cut section on the side
or rear casing panel to provide the opening in the required
position for the ue to pass through the casing.
Fit the cover panel (with the round ue exit hole) over the
chosen opening in the casing. Fit the circular rubber sealing
grommet provided into the circular hole in the cover panel
before tting the ue terminal section (or rst ue extension if
the ue is being extended using the green system).
4. Slacken the wing nuts holding the starter elbow and rotate
the elbow to the required direction for the ue to exit the
casing.
5. Push the end of the ue terminal section or ue extension
(with the red seal) from the outside of the boiler casing
through the sealing grommet in the casing panel. The
terminal section has been factory lubricated. Take care not to
dislodge or damage the red ue seal.
If using the low level ue option provided with the boiler:
6. Carefully insert the terminal into the starter elbow until the
bend of the terminal contacts the outer casing, then pull the
terminal forward approximately 25mm and rotate the bend so
that the outlet is horizontal.
Rear Exit - The ue must discharge away from the
building.
Side Exit - The ue should discharge towards the rear
of the casing to prevent ue gases re-entering the boiler
casing through the air inlet vents on the casing door.
The ue terminal must be tted horizontally to prevent
dripping from the end of the terminal.
If you are planning to extend the ue before terminating:
7. Carefully insert the rst extension/elbow piece into the starter
elbow and secure with a locking band.
8. Tighten the wing nuts holding the starter elbow and t the
stainless steel ue guard (if using low level ue option
provided with boiler) using the two screws provided.
9. The top panel of the casing has been designed so that it
may be tted to create a slight slope away from the side
positioned against the wall. To tilt the top panel, loosen the
four top panel casing screws and push down on the side
furthest from the wall. Tighten the screws. See Figure 4-1.
Figure 4-1: Standard low level ue provided with Outdoor Module
Section 4: Installation Page 13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grant Vortex Series and is the answer not in the manual?

Grant Vortex Series Specifications

General IconGeneral
BrandGrant
ModelVortex Series
CategoryBoiler
LanguageEnglish

Related product manuals