Super Free Match
Service Manual
MAINTENANCE
N
129
Long press “Fuc” key for more than 2s to enter the
first-level menu. The first-level menu includes
control unit and display unit.
Press “Enter” key to enter the second-level menu.
Press “Fuc” key to switch the menu.
Press “Back” key to the previous menu.
Control unit operation:
When entering into the control unit:
The function section flashes the running code and the data section display the current value uninterrupted.
Set parameters:
Press “Enter” key to enter the second-level menu, and set parameters with the ” “” keys. Now the
function section displays the running code uninterrupted and the data section flashes the set parameters.
Finish setting:
After press “Enter” key to the end, the function section will display the running code uninterrupted and the
data section
display the set parameters uninterrupted.
Back:
Press “Back” key to the previous menu, and long press the “Back” key to exit the operation.
Display unit operation:
When entering into the display unit:
The function section display running code uninterrupted and the data section display the current value
uninterrupted.
” “Keys are invalid in the operation.
If no operation is performed within 1min, it will automatically return to the normal display.
1.3.3 For example
Set condensation temperature
Long press “Fuc” key for more than 2s to enter the first-level menu: the function section flashes “CU”
code and the data section is blank.
Press “Enter” key to enter the second-level menu: the function section flashes “AE” code and the data
section display the current parameters.
Switch with the “Fuc” key to set condensation temperature: the function section flashes “AC” code and
the data section display the current parameters.
Press “Enter” key: the function section display “AC” code uninterrupted and the data section flashes the
current parameters.
Switch with the “” “to the target value, and then press “Enter” key: the function section display
“AC” code uninterrupted and the data section flashes the new parameters uninterrupted.
1.3.4 The meaning of running code