6.3 Connecting the second protective conductor
In some installation countries, a second protective conductor is required to prevent a
touch current in the event of a malfunction in the original protective conductor.For
installation countries falling within the scope of validity of the IEC standard 62109,
you must install the protective conductor on the AC terminal with a conductor
cross-section of at least 10 mm²Cu.Or Install a second protective conductor on the
earth terminal with the same cross-section as the original protective conductor on the
AC terminal. This prevents touch current if the original protective conductor fails.
6.4 Connecting the PV Array (DC input)
6.4.1 Conditions for DC Connection
The solar modules connected to the inverter must conform to the
Class A requirements of the IEC 61730 standard.
Please use the same brand male and female PV connectors.
MIN 7000-10000TL-X single-phase inverter has 3 independent input : MPPT1,
MPPT2 & MPPT3.
MIN 7000-8000TL-X(E) single-phase inverter has 2 independent input : MPPT1 &
MPPT2.