4. Enable or disable the alarm uploading and alarm voice warning function.
5. Set GPS settings.
(1) Select Longitude-Latitude Mode as Manual.
(2) Select longitude and latitude as East or West according to the actual position.
(3) Enter the value of longitude and latitude in three textboxes.
6. Click Point to North and save.
7. Enter the Initial Position Configuration interface:
Configuration > PTZ > Initial Position
Figure 5-22 PTZ Configuration
8. Click the PTZ control buttons to find a position as the initial position of the positioning system;
you can also call a defined preset and set it as the initial position of the positioning system.
9. Click Set to save the position.
Call/delete an Initial Position:
You can click to call the initial position. You can click to delete the initial position and
restore the factory default initial position.
5.3.2 Configuring Dynamic Fire Source Detection
Purpose:
When you enable this function and fire source or smoke is detected, the alarm actions will be
triggered. You can set different detection mode, fire source zoom mode, and so on.
Steps:
1. Enter Configuration>Advanced Configuration>System>VCA Resource Type to select Fire and
Smoke Detection as VCA Resource Type.
2. Enter the fire and smoke detection interface: