Section 11 - W7220 JADE™ Economizer Module
63-8594-02 Honeywell Economizers 116
Table 3. Menu Structure
Menu Parameter
Param-
eter
Default
Value
Parameter
Range and
Increments
Notes
STATUS ECON AVAIL NO YES/NO YES = economizing available; the system can use
Outdoor Air for free cooling when required.
ECONOMIZING NO YES/NO YES = Outdoor Air being used for 1st stage
cooling.
OCCUPIED NO YES/NO YES = OCC signal received from space
thermostat or unitary controller. YES = 24 Vac on
terminal OCC No = 0 Vac on terminal OCC.
HEAT PUMP n/ac COOL
HEAT
Displays COOL or HEAT when system is set to
heat pump (nonconventional)
COOL Y1-IN OFF ON/OFF Y1-I signal from space thermostat or unitary
controller for cooling stage 1. ON = 24 Vac on
term Y1-I OFF = 0 Vac on term Y1-I
COOL Y1-OUT OFF ON/OFF Cool Stage 1 Relay Output to mechanical cooling
(Y1-OUT terminal).
COOL Y2-IN OFF ON/OFF Y2-I signal from space thermostat or unitary
controller for second stage cooling. ON = 24 Vac
on term Y2-I OFF = 0 Vac on term Y2-I
COOL Y2-OUT OFF ON/OFF Cool Stage 2 Relay Output to mechanical cooling
(Y2-OUT terminal).
MA TEMP _ _._ ºF -40 to 150 ºF Displays value of measured mixed air from MAT
sensor. Displays --.- if not connected, short, or
out-of-range. Always 3F above MA LO Setpoint.
DA TEMP _ _._ ºF -40 to 150 ºF Displays when Discharge Air Sylk Bus sensor is
connected and displays measured discharge air
temperature. Displays --.-°F if sensor sends
invalid value, if not connected, short or out-of-
range.
OA TEMP _ _._ ºF -40 to 140 ºF Displays measured value of outdoor air
temperature. Displays --°F if sensor sends invalid
value, if not connected, short or out-of-range.
OA HUM _ _ % 0 to 100% Displays measured value of outdoor humidity from
QA Sylkbus sensor. Displays --% if not
connected, short, or out- of-range.
RA TEMP _ _._ ºF 0 to 140 ºF Displays measured value of return air temperature
from RAT sensor. Displays --°F if sensor sends
invalid value, if not connected, short or out-of-
range.
RA HUM _ _ % 0 to 100% Displays measured value of return air humidity
from RA Sylkbus sensor. Displays --% if sensor
sends invalid value, if not connected, short or out-
of-range.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Design and Application and is the answer not in the manual?

Honeywell Design and Application Specifications

General IconGeneral
BrandHoneywell
ModelDesign and Application
CategoryController
LanguageEnglish

Related product manuals