Section 3 - Types of Analog Economizers
35 Honeywell Economizers 63-8594-02
W6215, W7215 and W7460
The W6215A, W7215A and W7460A
economizer modules were similar to the
W6210 and W7210 with the addition of inputs
from a CO
2
sensor for Demand Control
Ventilation and contact inputs and outputs to
monitor and control various devices. The B
models included inputs from an outdoor CO
2
sensor for the function of limiting outdoor air
usage when the outdoor air was not suitable
for ventilation. The actuators used with these
controllers were:
• W6215 - Series 62
• W7215 - Series 72
• W7460 - M7415
Commercial
thermostat
One enthalpy or dry bulb and
one mixed/supply air sensor
required. Second enthalpy
sensor optional.
Series 62 or 72 or
M7415 Actuator
Optional room CO
2
sensor on A models,
additional optional
outdoor CO
2
sensors
on B models.
W6215, W7215,
W7460 install on
flat surface