Fire Alarm Control Panel IQ8Control C / M
100 FB 798951.10.GB0 / 04.15
10.3 Detector replacement
Replacement of fire and diagnostic detectors (4-zone module)
Diagnostic fire detectors can be replaced without adjustment of the detector address on the base circuit board or
overwriting data with the service PC. The menu options >Detector replacement< is inoperable for these detectors.
Replacement of intelligent detectors Series 9200 (loop)
Any number of detectors series 9200 / IQ8Quad or esserbus
®
transponders in an loop can be replaced. The
replacement of detectors can be carried out in many cases without the service PC. (See table)
At the control panel
Using the table on next page,
find out whether the replacement can be carried out
without the service PC.
At the control panel
no
yes
At the location
of the detector
Wait until the display "TEST"
for the primary loop go out.
Have malfunctions occurred?
no
Replacement of detectors is completed.
yes
Check the execution of the
replacement and reactivate
Replace detector function.
Switch the primary loop, detector
zone or detector. Replacement
of detectors is completed.
connect service-PC and
carry out automatic wiring
ring loop.
Enter the installation code, select primary loop
function, enter the primary loop number and select
function 4 "replace detector".
On the primary loop all zones and the Primary loop
are indicated on the display with "TEST"
Which trouble code appears
in the display ?
see section 11 (detector malfunctions).
no
yes
Exchange all detectors which are to be replaced
in the loop. Screw the new detectors tightly into
the detector bases, do not damage connecting cables.
Enter the installer code, select primary loop function,
enter the primary loop number and
select function 2 "swich off"
Is this malfuntion
due to the replacement
of detectors?
Fig. 87: Flow diagram of detector replacement

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control C and is the answer not in the manual?

Honeywell ESSER IQ8Control C Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control C
CategoryControl Panel
LanguageEnglish

Related product manuals