10.2 Testing (the loop)
Primary loop / transfer route
Primary loop : 121
Escape Function
1 Switch on / reset
2 Switch off
3 Test
4 Replace detector
Fig. 86: Testing the loop
Enter the number of the loop to be tested and press the Select function key.
Enter the number of the desired function (3 = Testing) or select the menu options >Test operation< with the
cursor keys and press the >Function< key.
An loop in test operation will not signal an alarm in the case of an event!
The Function >Testing< is not carried out when ...
the loop is switched off.
the loop module is defective.
Testing an loop
The test operation must be carried out individually for each loop or detector zone. The simultaneous testing of
several loops/detector zones is impossible.
By this menu point, the selected loop (including all detectors and esserbus
®
transponders) or single detector
zones in the loop are tested for the following functions:
Malfunctions of one or more detectors / esserbus
®
transponders.
Malfunction of the switch-on control (SOC) by automatic detectors.
Conformance of the addresses with the Customer data programming
(if necessary, the detector data is automatically updated).
Conformance of the loop wiring with the Customer data programming.
Conformance of detector types and external wiring with the Customer data programming.