EasyManuals Logo
Home>Honeywell>Control Panel>ESSER IQ8Control C

Honeywell ESSER IQ8Control C User Manual

Honeywell ESSER IQ8Control C
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15 79
8 Relay module
8.1 3-relay module / 3-relay common trouble module
Micro module for activating external devices (not potential free), with monitoring capability. You may connect up
to three external devices to this micro module.
Relay assignment is programmed with the service PC and Programming software tools 8000 software. For each
relay, you may enter a specific additional text comprising 25 characters per line for output on the display and
protocol printer.
Fig. 67: 3-relay module / 3-relay common trouble module
X 1
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K1, K2, K3
K 1 (for 3-relay common trouble module type used as common trouble relay)
K 2 and K 3 freely programmable, max. contact rating max. 30 V DC /1 A
S1, S2
coding switch for selecting monitored / non- monitored setting, or for special application
TEST
Test socket for in-factory adjustments only!
LED
No indicator function (in-factory testing purposes)
F1, F3, F5
Electronic fuse (multifuse): to reset, de-energise for approx. 30 seconds at the relevant screw
terminals on the terminal card

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control C and is the answer not in the manual?

Honeywell ESSER IQ8Control C Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control C
CategoryControl Panel
LanguageEnglish

Related product manuals