Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15 123
Trouble
text
Possible cause 1st. measure 2nd. measure
int. det. err
A dirty detector was found
during an EDD zone test.
Clean or replace detector. ---
reset
A detector could not be reset
during an EDD zone test.
Replace detector. ---
no SOC
The switch-on control of a
detector was impossible
during an EDD zone test.
Replace detector. ---
Addr. err.
A detector with Address 0 was
found during an EDD zone
test.
A non-addressable fire
detector has been connected
in an EDD detector zone.
the address board in the
detector base is defective or the
illicit address 0 has been
selected.
no 24V
Loss of line voltage for the
indicated module.
Check U
line
fuse and replace if
necessary.
Replace module.
DAC err.
Defective D/A converter in the
indicated module.
Replace module. ---
Request
No valid value can be
obtained from an EDD
detector zone or a monitored
relay
Voltage interference on the
line.
Check cable screening and
wiring.
U
linie
<
Loop voltage difference,
measured from A>B, is too
high. Sounder activation is
impossible.
Module damaged, loop
resistance too high.
check loop devices.
WireRes
Loop resistance too high.
Sounders are unable to
operate with full sound
pressure.
Check length of cable,
max. 3500 m for IQ8Quad
detector with consideration of
the load factor.
Check terminals from all loop
devices.
Err. 42 V
Loss of 42 V DC loop voltage.
mains supply not in +42 V DC
mode.
loop module damaged.
I-MesDef
Internal module failure. Module damaged. Sounder damaged.
base
The wireless base has been
removed from corresponing
detector base.
Insert wireless base in
detector base
---
Batt<30
Battery below rated voltage
Replace battery within 30
days
---
Batt<7
Battery below rated voltage Replace battery within 7 days ---

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control C and is the answer not in the manual?

Honeywell ESSER IQ8Control C Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control C
CategoryControl Panel
LanguageEnglish

Related product manuals