Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15 13
Configuration of FACP IQ8Control C
Connector 1
MM 1
A
Example 1:
Basic module with a micro module and a Field device module
(Part No.772479 without micro module slot) on slot 1 of the
Basic module.
Application:
With this configuration, for example, a single control panel
with an loop and max. 127 bus devices can be implemented.
Connector 1
MM 1
MM 2
B
Example 2:
Basic module with a micro module and a Field device module
(Part No.772477 with micro module slot) on slot 1 of the Basic
module
Application:
With this configuration, for example, a single control panel
with two loops and max. 254 bus devices can be implemented
or
This configuration is usually employed in essernet
®
networks
with an loop and max. 127 bus devices.
C
Connector 1
MM 1
MM 2
Example 3:
Basic module with a micro module and a Extension module
(Part No.772478 ) on slot 1 of the Basic module.
Application:
This configuration is usually employed in essernet
®
networks
with an loop and max. 127 bus devices.
Without the Field device module, no connection is
available for the fire department key pad and the
master box. These devices can be connected to a
different control panel of the essernet
®
.
Fig. 5: Configuration FACP IQ8Control C