LTE-CF Installation and Setup Guide
4
Compatibility
UL – Compatible Control Panels
VISTA-32FB FA1670C (First Alert)
VISTA-32FBT FA1670CT (First Alert)
VISTA-128FBP FA1700C (First Alert)
VISTA-128FBPT FA1700CT (First Alert)
VISTA-250FBP
VISTA-250BPT
UL – Compatible Receivers
7810iR-ENT Must be the primary alarm receiver.
8810iR Must be the primary alarm receiver.
MX8000 Can be used for supplemental reporting in ECP mode when connected to
model 7810iR-ENT.
Ademco 685 Can be used for supplemental reporting in ECP mode when connected to
model 7810iR-ENT.
7810PC Must be the primary alarm receiver
UL
The Automation System must be UL1981 listed.
Compliance
To meet UL864/NFPA, ensure the following:
It must be installed in accordance with NFPA (National Fire Protection Association)
standards 70 and 72.
It must be mounted in the same room and within 20 feet of the fire panel.
Conduit is required for all interconnections between the Fire Panel and communicator.
All equipment used for the IP connection (such as the router, hub, modem, etc.) shall be
listed, must be powered from an un-switched branch circuit, and be provided with
appropriate standby power.