Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 27
Programming Programming
Assign Message Priorities
Open the DVC Inputs branch of VeriFire Tools DVC programming, scroll down to the MN Active Tone Sequence. Assign the MN
Active Tone Category to the MN Active Tone sequence, and give it the priority just below the MN Category inputs. When MN is the
highest priority in the system, the MN Active Tone input will be the priority just above the Fire category of pages. When Fire is the high-
est priority in the system, the MN Active Tone input will be at the priority just above the General category of pages and sequences.
Figure 3.15 Assign Priority to the MN Active Tone Sequence
Priority 8, MN Active
Tone Category,
Sequence 2 (the MN
Active Tone)
Priorities 9 - 16,
Fire Message
Category
Priorities 1 - 7,
MN Message
Category
Example: MN has the highest
priority, and the MN Active Tone
Category has been assigned to Input
31, the MN Active Tone (Message
Sequence 1 from Figure 3.14). It has
been assigned a priority of 8, just
below the MN Category inputs and
above the Fire Category inputs.
Change priority of inputs with the Up and Down buttons.
Input number is display and sort only.