16 PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
Installation FACP with PSE Power Supply in Slave Mode
2.5 FACP with PSE Power Supply in Slave Mode
In this application, an PSE power supply, configured as a Slave unit, is connected to a master FACP programmed for synchronized out-
put. .
The following notes apply to Figure 2.7 on page 16
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Use only devices from the same manufacturer in each system.
3. Set Output DIP Switch: position 3=ON, 4 = OFF, 5 = ON, 6 = OFF.
4. If the FACP has a dedicated sync output connector, wire the remote sync output connector to Input #1 terminals 2 and 3.
5. Input#1 is mapped to Slave mode output in this example, but it can programmed to another input using the DIP switches.
6. Notification appliances cannot be installed on the FACP control circuit connecting to the PSE input circuits.
2.6 PSE Power Supply in Master Mode Connected to FACP
In this application, a master PSE power supply, set for synchronization, is connected to an FACP with non-synchronized output.
The following notes apply to Figure 2.8.
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Set Output DIP switches to the desired sync protocol as described below. Refer to the Device Compatibility Document for
compatible devices.
TB15
PSE
FACP
NAC programmed for sync
or remote sync output
ELR for
FACP
NAC
Figure 2.7 Supervised Master/Slave Connections
DIP Switch Position
Synchronization Type
3456
ON OFF ON OFF Slave mode (NAC follower)
OFF
ON ON OFF Master mode - ANSI Temporal (Temporal 3)
ON ON ON OFF Master mode - CO Temporal (Temporal 4)
OFF OFF OFF
ON Master mode - Amseco/Potter
OFF
ON OFF ON Master mode - Gentex
OFF OFF
ON ON Master mode - System Sensor
OFF
ON ON ON Master mode - Wheelock
ON OFF OFF ON Master mode, Selective Silence - Amseco/Potter
ON ON OFF ON Master mode, Selective Silence - Gentex
TB15
PSE
Figure 2.8 Supervised FACP to Master Connections (non-synchronized source)
FACP
(also can be triggered by a
control module or relay module)
NAC with no synchronization
NAC1
ELR for
FACP
NAC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER PSE-10 and is the answer not in the manual?

Honeywell NOTIFIER PSE-10 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER PSE-10
CategoryExtender
LanguageEnglish

Related product manuals