38 PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
Application Examples Controlling NACs For Sync Follower Operation Using a Control Module
B.2 Controlling NACs For Sync Follower Operation Using a Control Module
In this application, the power supply has been set to operate in slave mode and will follow the sync signal from the FACP. This applica-
tion requires Input #1 to be controlled by the FACP sync output. Input #1 may be wired to the next PSE or terminate in and ELR. Input
#2 (or Input #3, if available) will act as the trigger signal for the output circuits. The control module can be powered by one of the PSE
output circuits, configured as aux power (24VDC). See Table 3.14 on page 27 DIP switch settings.
The following notes apply to Figure B.2.
When the PSE power supply is in an inactive state (control module not active), a trouble on the NAC circuits mapped to TB6 will
result in an open circuit condition on the control module output circuit (monitored by End-of-Line Resistor across TB6, Terminals 1
and 4). As an alternative, the trouble contacts at TB1 of the power supply can also be used for limited trouble monitoring excluding
faults reported by Command Input #2 related to Command Input#1 configured for Sync Input mode. Refer to Section 5 for more
information.
Refer to Section 3 for instructions on setting the DIP switches.
Output faults are reported via Command Input#2 with Command Input#1 configured for Sync Input mode operation.
Refer to the FACP manual for load restrictions and line length limitations when wiring multiple power supplies at the input.
Wire NACs as shown on page 13.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
An End-of-Line Resistor must be installed across all input circuits, Terminals 1 and 4, for control module wiring supervision (the
ELR value is dependent on the module/FACP employed).
For a list of compatible devices, refer to the Notifier Device Compatibility Document #15378.
Refer to the SLC Wiring Manual for more information.
NO NC C NO NC C
TB4
TB15
T
B
2
T
B
1
T
B
1
3
T
B
1
2
T
B
1
1
T
B
1
0
T
B
9
T
B
8
T1
T11
T2
T10
T3
T9
T4
T8
T5
T7
T6
Figure B.2 Controlling Multiple Outputs with One Input as Sync Follower
Control Module*
SLC
*If the SLC device does not match
the one in this figure, refer to the
SLC manual wiring conversion
charts for legacy and newer ver-
sions of the modules.
NAC Output Circuits
24VDC power output
NAC Sync
FACP
to next PS Series
Power Supply or ELR

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER PSE-10 and is the answer not in the manual?

Honeywell NOTIFIER PSE-10 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER PSE-10
CategoryExtender
LanguageEnglish

Related product manuals